Input linearization, 14 input linearization, General software – Watlow Series 988 User Manual

Page 130

Advertising
background image

8.14

WATLOW Series 988 User’s Manual

General Software Features, Chapter 8

General Software

Input Linearization

Requirements
The square root extraction feature is standard on any Series 988 con-
troller with universal signal conditioner inputs. The linearization prompt
will appear if a process input is selected with the DIP switches (see
Chapter 1).

Overview
In many flow applications the output signal from a flow transmitter repre-
sents a squared value of the actual flow. The square root must be extract-
ed from the signal to make it useful to the operator. Many flow transmit-
ters offer this feature in the transmitter itself, but this can add significant-
ly to the cost. Using the square root extraction option in the Series 988
controller can save the operator money. The feature is enabled simply by
setting input 1 linearization

[lin1] or input 2 linearization [lin2] to

square root extraction

[root].

Advertising