W a t l o w S e r i e s P D

9

C h a p t e r 2 I n s t a l l a n d W i r e

Ó

Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.

ç

WARNING: Process input may
not have sensor break protec-
tion. Outputs can remain full on.

Note: Install a 1k

pull-down

resistor for each digital in-
put using voltage inputs.

Note: Install a 10k

pull-up re-

sistor for each digital input
using contact closure in-
puts.

Figure 9a —

Input 1, 0 to 20 mA Process Input

(all model numbers)

• Input impedance 100

, dc only

• Controller does not supply power for the current loop

Figure 9b —

Input 2, 0 to 20 mA Process Input

PDD _-_ _ _ _-_ _ _

• Input impedance 100

, dc only

• Controller does not supply power for the current loop

• Input 2 isolated from Input 1

Dual Digital Inputs

PD_ 1-_ _ _ _-_ _ _

• Input impedance 10k

, dc only

• Input 2 isolated from Input 1

Figure 9c —

Voltage input

0-1VÎ (dc) Event Input Low State

2-36VÎ (dc) Event Input High State

Figure 9d —

Contact closure

0-2k

Event Input Low State

> 7k

Event Input High State

1

2 3 4

4

1

+5V‡ (dc)

2

3

Digital Common

Digital Input 1

Digital Input 2

10k

10k

Add a 10k

pull

up resistor for each
active input

1

2 3 4

1

2

3

Digital Common

Digital Input 1 +

Digital Input 2 +

-

1k

1k

Add a 1k

pull

down resistor for
each active input

5

6 7 8

7

5

+

-

9

10 11 12

11

9

+

-