C h a p t e r 5 T r o u b l e s h o o t i n g

Indication

Probable Cause(s)

Corrective Action

Alarm will not activate or
clear.

• Controller is in Error condition.

• Alarm is in latched setting.

• Alarm is silenced.

• Incorrect configuration.

• Incorrect wiring.

• Wrong output type.

• Defective controller.

• Determine cause of error and correct.

• Wait for process to return to normal
and acknowledge alarm.

• Wait for process to return to normal
and alarm will work correctly.

• Configure Alarm, Alarm Set Point, Hys-
teresis, Silencing and Latching.

• Correct wiring.

• Replace controller with correct output
type.

• Repair or replace controller.

Controller's process value
reading is decreasing as the
actual process is increasing.

• Thermocouple is reversed wired.

• Analog voltage or current input scal-
ing is reversed.

• Check thermocouple wire for correct po-
larity.

• Configure correct scaling on Input page.

Controller does not control
close enough to set point.

• PID values incorrect.

• Cycle times incorrect.

• Heat or cooling capacity incorrectly
sized for application.

• Incorrect sensor placement.

• Controller is in Manual mode (open
loop).

• Control loop action configured incor-
rect.

• Tune controller (Auto Tune or Manual
Tune).

• Set cycle time to match hardware on
Control Loop .

• Size energy sources to match load.

• Place sensor in optimal location.

• Change to Auto mode (closed loop) on
Monitor page.

• Configure Control Loop Action on Con-
trol Loop page.

Output cycles (turns on and
off) too frequently.

• Wrong control mode. PID control se-
lected instead of ON-OFF control.

• The cycle time is set too short.

• Activate ON-OFF control on Output
page.

• Increase Output Cycle Time on Out-
put page.

Cannot access Security, Mon-
itor, Configuration or Cali-
bration page.

• Password is enabled and incorrect
password is supplied.

• Provide the correct user name and pass-
word.

Process value reads incor-
rectly

• Analog input is configured incorrectly.

• Thermocouple sensor shorted.

• Process sensor scaled incorrectly.

• Calibration offset is incorrect.

• Sensor is wired incorrectly.

• Controller calibration is incorrect or
corrupt.

• Defective controller.

• Configure control for appropriate sen-
sor input on Analog Input page.

• Repair wiring or replace sensor.

• Set scaling on Analog Input page.

• Correctly set calibration offset.

• Wire sensor per wiring section.

• Recalibrate controller.

• Repair or replace controller.