Voltage process input procedure, Current process input procedure, Input x (1 to 3) setup and calibration – Watlow Series F4S/D User Manual

Page 109

Advertising
background image

Wa t l o w S e r i e s F 4 S / D

C a l i b r a t i o n

9 . 3

Voltage Process Input Procedure

Equipment
• Precision voltage source, 0 to 10V minimum

range, with 0.001V resolution.

Input x (1 to 3) Setup and Calibration

1. Connect the correct power supply to terminals

1, 2 and 3 (see the Wiring Chapter and the

Appendix).

Input 1

2. Connect the voltage source to terminals 59 (+)

and 62 (-) of the controller.

3. Enter 0.000V from the voltage source to the

controller. Allow at least 10 seconds to stabilize.

Press the Right Key . once at the Calibrate

Input 1 prompt. At the 0.000V prompt press .

once and to store the 0.000V input press the Up

Key > once.

4. Enter 10.000V from the voltage source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 1 prompt.

At the 10.000V prompt press . once and to

store the 10.000V input press > once.

Input 2

5. Connect the voltage source to terminals 53 (+)

and 58 (-) of the controller.

6. Enter 0.000V from the voltage source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 2 prompt.

At the 0.000V prompt press . once and to

store the 0.000V input press > once.

7. Enter 10.000V from the voltage source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 2 prompt

(Factory Page). At the 10.000V prompt press .

once and to store the 10.000V input press >

once.

Input 3

8. Connect the voltage source to terminals 51 (+)

and 56 (-) of the controller.

9. Enter 0.000V from the voltage source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 3 prompt.

At the 0.000V prompt press . once and to

store the 0.000V input press > once.

10. Enter 10.000V from the voltage source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 3 prompt

(Factory Page). At the 10.000V prompt press .

once and to store the 10.000V input press >

once.

11. Rewire for operation and verify calibration.

Current Process Input Procedure

Equipment
• Precision current source, 0 to 20mA range, with

0.01mA resolution.

Input x (1 to 3) Setup and Calibration

1. Connect the correct power supply to terminals

1, 2 and 3 (see the Wiring Chapter and the

Appendix).

Input 1

2. Connect the current source to terminals 60 (+)

and 62 (-).

3. Enter 4.000mA from the current source to the

controller. Allow at least 10 seconds to stabilize.

Press the Right Key . once at the Calibrate

Input 1 prompt. At the 4.000mA prompt press
.

once and to store 4.000mA press the Up Key

>

once.

4. Enter 20.000mA from the current source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 1 prompt.

At the 20.000mA prompt press . once and to

store 20.000mA press > once.

Input 2

5. Connect the current source to terminals 54 (+)

and 58 (-).

6. Enter 4.00mA from the current source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 2 prompt.

At the 4.000mA prompt press . once and to

store 4.000mA press > once.

7. Enter 20.00mA from the current source to the

controller. Allow at least 10 seconds to stabilize.

Press . once at the Calibrate Input 2 prompt.

At the 20.000mA prompt press . once and to

store 20.000mA press > once.

Input 3

8. Connect the voltage source to terminals 52 (+)

and 56 (-) of the controller.

9. Enter 4.000mA from the current source to the

controller. Allow at least 10 seconds to stabilize.