Operations page parameter table, Pid set x (1 to 5)* (optional inner loop), Edit pid – Watlow Series F4S/D User Manual

Page 27: Autotune pid cascade, Autotune pid

Advertising
background image

Wa t l o w S e r i e s F 4 S / D

O p e r a t i o n s

3 . 1 1

Operations Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear

*This section is also applicable for Cascade Inner Loop.
NOTE: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.

Active if PID Units (Setup Page)

is set to SI and Proportional

Band is not set to 0.

1A

1B Set

503 553 [1]

513 563 [2]

523 573 [3]

533 583 [4]

543 593 [5]

r/w

0.00 minutes

(0)

0.00 to 9.99 minutes

(0 to 999)

Derivative x (A or B)

Set the derivative

time.

Active if PID Units (Setup Page)

is set to U.S. and Proportional

Band is not set to 0.

1A

1B Set

502 552 [1]

512 562 [2]

522 572 [3]

532 582 [4]

542 592 [5]

r/w

0 per minute

(0)

0.00 per minute to

99.99 per minute

(0 to 9999)

Reset x (A or B)

Set the reset time in

repeats per minute.

Active if PID Units (Setup Page)

is set to SI and Proportional

Band is not set to 0.

1A

1B Set

501 551 [1]

511

561 [2]

521 571 [3]

531 581 [4]

541 591 [5]

r/w

0 minutes

(0)

0.00 to 300.00 minutes

(0 to 30000)

Integral x (A or B)

Set the integral time

in minutes.

Active: Always (Channel 1).

°F Default for US

°C Default for SI

1A

1B Set

500 550 [1]

510 560 [2]

520 570 [3]

530 580 [4]

540 590 [5]

r/w

25°F (25)

14°C (14)

0 to 30000

(0 to 30000)

Proportional Band x (A or B)

Define the propor-

tional band for PID

control.

Main > Operations > Edit PID > PID Set Channel 1 > PID Set x (1 to 5)

PID Set x (1 to 5)* (Optional Inner Loop)

Main > Operations > Edit PID

Edit PID

Active if Analog Input 3 Control

Type is set to Cascade.

343

r/w

Tune Off (0)

Tune Off (0)

Outer Loop PID Set 1 (1)

Outer Loop PID Set 2 (2)

Outer Loop PID Set 3 (3)

Outer Loop PID Set 4 (4)

Outer Loop PID Set 5 (5)

Cascade Outer Loop

Select which PID pa-

rameters will be au-

tomatically tuned.

Active if Analog Input 3 Control

Type is set to Cascade.

305

r/w

Tune Off (0)

Tune Off (0)

Inner Loop PID Set 1 (1)

Inner Loop PID Set 2 (2)

Inner Loop PID Set 3 (3)

Inner Loop PID Set 4 (4)

Inner Loop PID Set 5 (5)

Cascade Inner Loop

Select which PID pa-

rameters will be au-

tomatically tuned.

Main > Operations > Autotune PID > Cascade

Autotune PID Cascade

Active: Always (Channel 1).

Active if controller is set to Dual

Channel Ramping (Channel 2).

Channel

305

[1]

324

[2]

r/w

Tune Off (0)

Tune Off (0)

Ch1 PID Set 1 (1)

Ch1 PID Set 2 (2)

Ch1 PID Set 3 (3)

Ch1 PID Set 4 (4)

Ch1 PID Set 5 (5)

Ch2 PID Set 6 (1)

Ch2 PID Set 7 (2)

Ch2 PID Set 8 (3)

Ch2 PID Set 9 (4)

Ch2 PID Set 10 (5)

Channel x (1 to 2) Autotune

Select whether PID

parameters will be

automatically

selected.

Main > Operations > Autotune PID

Autotune PID