Watlow Series SD6 Limit With Devicenet User Manual

Page 8

Advertising
background image

Wa t l o w S e r i e s S D 6 L i m i t w i t h D e v i c e N e t

8

Table 15. Connection Object Instance Attributes

Attribute #

Access Rule

Name

DeviceNet Data
Type

Description of
Attribute

Semantics of Values

1

Get

State

USINT

State of the object

2

Get

Instance Type

USINT

Indicates either
I/O or Messaging

3

Get

Transport Class
Trigger

BYTE

Defines behaviour
of the Connection

4

Get

Produced
Connection ID

UINT

Placed in CAN
Identifier Field
when the
Connection trans-
mits

5

Get

Consumed
Connection ID

UINT

CAN Identifier
Field value that
denotes message to
be received

6

Get

Initial Comm
Characteristics

BYTE

Defines the
Message Group(s)
across which pro-
ductions and con-
sumption associat-
ed with this
Connection when it
occurs

7

Get

Produced
Connection Size

UNIT

Maximum number
of bytes transmit-
ted across this
Connection

8

Get

Consumed
Connection Size

UNIT

Maximum number
of bytes received
across this
Connection

9

Get/Set

Expected
Packet Rate

UNIT

Will round up to
the next 100 mSec.
Increment.

12

Get/Set
(set for
explicit
messaging
only)

Watchdog
Timeout Action

USINT

Defines how to
handle
Inactivity/Watchdo
g timeouts

For Explicit
Connection only:

1 = Auto Delete
3 = Deferred
Delete

Advertising