Device configuration inputs, Inputs, Input value – Watlow Series PD User Manual

Page 65: Actual analog input value for inputs 1 and 2, Control loop process value

Advertising
background image

W a t l o w S e r i e s P D

63

C h a p t e r 9 D e v i c e C o n f i g T a b l e

Device Configuration > Inputs > Analog Inputs 1 and 2, CT Inputs 3 and 4

Analog Input 1 - Process ValueDisplay analog input unfiltered process value.,Monitor DeviceTrend Information,,-2000000200 to
2000000200,0,31-32 (R) (/1000)
Analog Input 2 - Process ValueDisplay analog input unfiltered process value.,Monitor DeviceTrend Information,,-2000000200 to
2000000200,0,43-44 (R) (/1000)
Analog Input 3 - Process ValueDisplay analog input unfiltered process value.,Monitor DeviceTrend Information,,-2000000200 to
2000000200,0, (R)
Analog Input 4 - rocess ValueDisplay analog input unfiltered process value.,Monitor DeviceTrend Information,,-2000000200 to
2000000200,0, (R)
Analog Input 1 - Filtered Process ValueDisplay analog input filtered process value.,Monitor DeviceTrend Information,,-2000000200 to
2000000200,0,33-34 (R) (/1000)
Analog Input 2 - Filtered Process ValueDisplay analog input filtered process value.,Monitor DeviceTrend Information,,-2000000200 to
2000000200,0,45-46 (R) (/1000)
Analog Input 3 - Filtered Process ValueDisplay analog input filtered process value.,Monitor DeviceTrend Information,,-2000000200 to
2000000200,0, (R) (/1000)
Analog Input 4 - Filtered Process ValueDisplay analog input filtered process value.,Monitor DeviceTrend Information,,-2000000200 to
2000000200,0, (R) (/1000)
Analog Input 1 - ctive Process ValueDisplay analog input process value displayed on web page and used by control loop.,Monitor Device-
Trend Information,,-2000000200 to 2000000200,0,35-36 (R) (/1000)
Analog Input 2 - Active Process ValueDisplay analog input process value displayed on web page and used by control loop.,Monitor Device-
Trend Information,,-2000000200 to 2000000200,0,47-48 (R) (/1000)
Analog Input 3 - Active Process ValueDisplay analog input process value displayed on web page and used by control loop.,Monitor Device-
Trend Information,,-2000000200 to 2000000200,0,53-54 (R) (/1000)
Analog Input 4 - Active Process ValueDisplay analog input process value displayed on web page and used by control loop.,Monitor Device-
Trend Information,,-2000000200 to 2000000200,0,57-58 (R) (/1000)

Parameter Name

and Description

Web Page

Your

Settings

Range

Default

Modbus*

(Read/write and

scaling)

Analog Input 1 - Process Value

Display analog input unfil-
tered process value.

Monitor Device
Trend Information

-2000000200 to 2000000200
degrees or units

31-32 (R) (/1000)

Analog Input 2 - Process Value

Display analog input unfil-
tered process value.

Monitor Device
Trend Information

-2000000200 to 2000000200
degrees or units

43-44 (R) (/1000)

Analog Input 3 - Process Value

Display analog input unfil-
tered process value.

Monitor Device
Trend Information

-2000000200 to 2000000200
units

(R)

Analog Input 4 - Process Value

Display analog input unfil-
tered process value.

Monitor Device
Trend Information

-2000000200 to 2000000200
units

(R)

Analog Input 1 - Filtered
Process Value

Display analog input filtered
process value.

Monitor Device
Trend Information

-2000000200 to 2000000200
degrees or units

33-34 (R) (/1000)

Analog Input 2 - Filtered
Process Value

Display analog input filtered
process value.

Monitor Device
Trend Information

-2000000200 to 2000000200
degrees or units

45-46 (R) (/1000)

Analog Input 3 - Filtered
Process Value

Display analog input filtered
process value.

Monitor Device
Trend Information

-2000000200 to 2000000200
units

(R)

Analog Input 4 - Filtered
Process Value

Display analog input filtered
process value.

Monitor Device
Trend Information

-2000000200 to 2000000200
units

(R)

Analog Input 1 - Active
Process Value

Display analog input process
value displayed on web page
and used by control loop.

Monitor Device
Trend Information

-2000000200 to 2000000200
degrees or units

35-36 (R) (/1000)

Analog Input 2 - Active
Process Value

Display analog input process
value displayed on web page
and used by control loop.

Monitor Device
Trend Information

-2000000200 to 2000000200
degrees or units

47-48 (R) (/1000)

Analog Input 3 - Active
Process Value

Display analog input process
value displayed on web page
and used by control loop.

Monitor Device
Trend Information

-2000000200 to 2000000200
units

53-54 (R) (/1000)

Analog Input 4 - Active
Process Value

Display analog input process
value displayed on web page
and used by control loop.

Monitor Device
Trend Information

--2000000200 to 2000000200
units

57-58 (R) (/1000)

Advertising