W a t l o w S e r i e s P D

7

C h a p t e r 2 I n s t a l l a n d W i r e

Ó

Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.

Figure 7a —

Thermocouple Input 1

(all model numbers)

Thermocouples are polarity sensitive. The negative lead (usually red) must be
connected to terminal 9.

• Input impedance: >20 M

Figure 7b —

Thermocouple Input 2

PDD _-_ _ _ _-_ _ _ _

Thermocouples are polarity sensitive. The negative lead (usually red) must be
connected to terminal 5.

• Input impedance: >20 M

• Input 2 isolated from Input 1

Figure 7c —

2-Wire RTD Input 1 (100

DIN curve 0.00385

/

/°C)

(all model numbers)

Terminals 9 and 11 must be shorted for a two-wire RTD.

• Nominal excitation current: 250

µ

A

Figure 7d —

3-Wire RTD Input 1 (100

DIN curve 0.00385

/

/°C)

(all model numbers)

The S1 lead (usually white) must be connected to terminal 10.

• Nominal excitation current: 250

µ

A

9

10 11 12

10 S1

11 S2

9 S3

12 INFOSENSE-P™ DATA

INFOSENSE-P™ GND

9

10 11 12

10 S1

11 S2

9 S3

9

10 11 12

10 S1

11 S2

9

5

6 7 8

6 +
5

-

8 INFOSENSE-P™ DATA

INFOSENSE-P™ GND

5

6 7 8

6 +
5

-

9

10 11 12

10 +

9

-

12 INFOSENSE-P™ DATA

INFOSENSE-P™ GND

9

10 11 12

10 +

9

-