Toxalert BSP User Manual

Page 2

Advertising
background image

FEATURES:

LOW VOLTAGE CONTROL CIRCUITRY
Flow

Switch and outside air thermostat operation

(24VAC).

LIGHT EMITTING DIODES

(LED’s) for

status indication, long life, maintenance free
operation.
1) POWER ON – (Green)

2) FLOW NORMAL – (Green)

3) FAILURE – (Red)

SPDT CONTACTS FOR REMOTE
ALARM ANNUNCIATION

ALL MODELS

will operate on 120, 208 or 240

VAC

ON-OFF-AUTO OPERATION:

AUTO – requires outdoor air thermostat to activate
sequencer circuits.

OFF – positive OFF of system.

ON – positive On of system, bypasses the outdoor
air thermostat.

REMOTE CONTROL:

Lead/Lag switch and ON-OFF-AUTO switch
functions can easily be operated remotely (low
voltage.

FIELD PROGRAMMABLE TIME DELAY:

Delay of lag function operation. Pump controller
time delay from 10 seconds to 3 minutes. Boiler
controller 30 seconds to 16 minutes.

STANDARD MODELS:

The PSP, Pump Sequence Panels are available in four models, Model PSP-10 & PSP-12 are electronic
controllers housed in a 12″ W x 14″ H x 4″ D surface mount enclosure with key locking hinged door.
Models PSP-10 CM and PSP-12 CM are electronic controllers mounted on a 10.5″ W 2 14″ H steel
mounting plate for incorporation into a custom control panel. The PSP models also come with two
different output relay contact ratings, PSP-10 and PSP-10CM models have contacts rated for 15 A. at
120/220 VAC, and the PSP-12 and PSP-12 CM contacts are rated for 30A at 120/220 VAC.

Model Numbers are:

PSP-10 and PSP-10CM*
PSP-12 and PSP-12CM*

The BSP, Boiler Sequence Panels, controllers are also available with and without surface mount
enclosures. The Model BSP-15 controller is housed in a 12″ W x 14″ H x 4″ D surface mount
enclosure with key locking hinged door and BSP-15 CM controller is mounted on a 10.5″ W x 14″ H
steel mounting plate. Both models have an output relay contact rating of 15A at 120/220VAC.

Model Numbers are:
BSP-15 and BSP-15CM*

*CM=Custom mount (controller mounted on steel plate

for incorporation into custom panel.)

TIMING:

All PSP-10 and 12 controllers are shipped from the factory with a 30 seconds delay and all BSP-15
controllers are shipped from the factory with a 6 minutes delay unless other time delay period is
requested. The time delay period starts when the outdoor air thermostat calls for pump/boiler to start,
or if the On-Off-Auto switch is switched to “On”. If the pump/boiler does not proof operation within
the time delay period then the standby pump/boiler is turned on by the controller.