Table #1 table #2, Required auxiliary equipment (supplied by others), Lead/lag controller external wiring – Toxalert BSP User Manual

Page 4

Advertising
background image

TABLE #1

TABLE #2

* TR resistors are mounted on the Timing Registor (TR) terminal strip (TB3) which is mounted on the P.C. board. ⅛ or ¼
watt resistors may be used.

** Time delay of standard units.

REQUIRED AUXILIARY EQUIPMENT (Supplied by Others)

A) SPDT Differential Pressure Switch or Flow Switch

Suggest: Robertshaw PF-126 Floating D Differential Pressure switch or
Penn P74FA-5 pressure Differential Switch.

B) Outside air thermostat for “AUTOMATIC” operation.

Suggest: Honeywell T675, or Columbus Electric LB100 (SPST) or LB200 (DPST) remote bulb thermostats, or TC-100
series remote bulb controllers from Dynacon. Toxalert has controlling devices you need for application. Please call.

LEAD/LAG CONTROLLER EXTERNAL WIRING

PSP-10 & PSP-12

TR VALUES IN OHMS RESULTING TIME DELAY

100K

10 seconds

300K

30 seconds **

620K

1 minute

1.2 meg

2 minutes

1.8 meg

3 minutes

2.4 meg

4 minutes

BSP-15 & BSP-15CM

TR VALUES IN OHMS RESULTING TIME DELAY

100K

30 seconds

200K

1 minute

360K

2 minutes

560K

3 minutes

750K

4 minutes

910K

5 minutes

1.2 meg

6 minutes **

1.3 meg

7 minutes

1.5 meg

8.25 minutes

1.8 meg

10 minutes

2.0 meg

11 minutes

3.0 meg

16 minutes

TOXALERT INTERNATIONAL, Inc.,

PO Box 159, Mound, MN. 55364 PHONE: (952) 472-4541 • FAX: (952) 472-4960

www.toxalert.com