Table7.2

Field Diagnostic Alert

Indication of FD_*_ACTIVE

Indication of FD_RECOMMEN_ACT

Solution

Electronics failure

Repair electronics

Replace electrical parts e.g. amplifier.

Or contact sales office or service center.

Sensor/Actuator failure

Repair Sensor/Actuator

Replace mechanics e.g. sensor or

actuator. Or contact sales office or service

center.

Potential failure

Investigate failure

Perform reconfiguration, cleaning, wiring/

connector or electrical board check.

If alarm still persists, contact sales office or

service center.

Backup function in operation

Repair primary side

Repair primary sensor before backup

sensor fails.

Firmware update error

Retry updating firmware

Retry firmware update. Check cause of the

failure if alarm persists.

Communication configuration error Configure communication correctly

Correct configuration of communication.

Non-operating-state

Wait for a while

Wait for a while. Check cause of the failure

if alarm persists.

Calibration warning

Check calibration

Investigate cause of failure and recalibrate

device.

Device configuration error

Configure device correctly

Correct configuration relating to sensor or

actuator.

Function restricted

Confirm the state

Check if this is right state.

Simulation mode

Confirm the state

Check if this is right state.

Manual mode

Confirm the state

Check if this is right state.

Function Block notice

Check Function Block status

Check conditions of function blocks. In

order to avoid alarm from unused function

blocks, configure RESOURCE2.FD_

EXTENDC_MAP_n (n: 1 to 3) parameter.

Sensor/Actuator out of range

Check specification

Check specification of sensor and

actuator. Or process conditions may be

temporarily non-conforming.

Out of operating limit

Check environment

Check environment specification of sensor

and actuator. Or process environment may

be temporarily non-conforming.

Temporal decrease of value quality Check process or peripherals

Check process and peripherals conditions.

Deterioration estimated by Time

Based Maintenance

Check deterioration

Check if maintenance is required.

Deterioration estimated by

Condition Based Maintenance

Check deterioration

Check if maintenance is required.

Impulse Line Blockage Detected

Check process and impulse line

condition

1.Check process and impulse line

condition.

2.If there are large flow change or the

change of fluid under the measured

process conditions, obtain the

reference value again.(Please follow

the operation procedure in User

Manual)

Heat Trace Warning Detected

Check the heater failure

1.Check the heater failure.

2.Check the capsule temp. and Amplifier

temp.

3.Adjust Flg Temp Coef(STB.FLG_

TEMP_COEF).

Optional function configuration error Check optional configuration

Check configuration of optional functions.

Alarm related information

Confirm information

Check the alarm related information.

Process alarm

Check process

Check process conditions.

CHECK

CHECK

Check both modes for the SENSOR and

LCD transducer blocks are AUTO.