Yokogawa EJX930A User Manual

Page 60

Advertising
background image

<8. Device Information>

8-3

IM 01C25T02-01E

Table 8.5

Contents of DEVICE_STATUS_5

(index 1049)

Hexadecimal

Display

through DD

Description

NAMUR

NE-107

category

0x80000000

Diff Pressure

Span Trim

Error

(AL-50)

Trimming range

error for differential

pressure span

C

0x40000000

Diff Pressure

Zero Trim

Error

(AL-50)

Trimming range

error for differential

pressure zero

C

0x20000000

Static

Pressure

Span Trim

Error

(AL-51)

Trimming range

error for static

pressure span

C

0x10000000

Static

Pressure

Zero Trim

Error

(AL-51)

Trimming range

error for static

pressure zero

C

Table 8.6

Contents of DEVICE_STATUS_6

(index 1050)

Hexadecimal

Display

through DD

Description

NAMUR

NE-107

category

0x80000000

PID in O/S

Mode (AL-

70)

PID block is in O/S

mode

C

0x40000000

PID in MAN

Mode (AL-

70)

PID block is in MAN

mode

C

0x20000000

PID Not

Scheduled

(AL-70)

PID block is not

Scheduled

C

0x10000000

PID in

Bypass

Mode

PID Block is in

Bypass mode.

C

0x08000000

SC in O/S

Mode (AL-

71)

SC block is in O/S

mode

C

0x04000000

SC in MAN

Mode (AL-

71)

SC block is in MAN

mode

C

0x02000000

SC Not

Scheduled

(AL-71)

SC block is not

scheduled

C

0x01000000

IT in O/S

Mode (AL-

72)

IT block is in O/S

mode

C

0x00800000

IT in MAN

Mode (AL-

72)

IT block is in MAN

mode

C

0x00400000

IT Not

Scheduled

(AL-72)

IT block is not

scheduled

C

0x00100000

IS in O/S

Mode (AL-

73)

IS block is in O/S

mode

C

0x00080000

IS in MAN

Mode (AL-

73)

IS block is in MAN

mode

C

Hexadecimal

Display

through DD

Description

NAMUR

NE-107

category

0x00040000

IS Not

Scheduled

(AL-73)

IS block is not

scheduled

C

0x00020000

AR in O/S

Mode (AL-

74)

AR block is in O/S

mode

C

0x00010000

AR in MAN

Mode (AL-

74)

AR block is in MAN

mode

C

0x00008000

AR Not

Scheduled

(AL-74)

AR block is not

scheduled

C

0x00000004

IT Total

Backup Err

(AL-78)

IT Total Backup

has failed. Last IT

Output Value (IT.

LAST.VALUE) is

not saved.

F

0x00000002

LCD Display

Outside

Range Limit

(AL-79)

Displayed value

exceeds limit

C

0x00000001

LCD Display

Config Error

(AL-79)

Specified settings

for Display do not

meet the conditions

C

Table 8.7

Contents of DEVICE_STATUS_7

(index 1051) (Applicable for option

code "DG1".)

Hexadecimal

Display

through DD

Description

NAMUR

NE-107

category

0x00004000

Flg Temp

High Alarm

(AL-87)

Flange

Temperature High

Alarm occurs.

M

0x00002000

Flg Temp

Low Alarm

(AL-87)

Flange

Temperature Low

Alarm occurs.

M

0x00001000

Outside

Diagnosis

Range (AL-

89)

Outside Diagnosis

Range.

0x00000800

Invalid Ref

fDP (AL-88)

VALUE_FDP

under normal

conditions is not

up to the reference

fluctuation

level required

to blockage

detection.

C

0x00000400

Invalid Ref

fSPl (AL-88)

VALUE_FSPL

under normal

conditions is not

up to the reference

fluctuation

level required

to blockage

detection.

C

Advertising