4 tiis certification, 5 iecex certification, Tiis certification -11 – Yokogawa YTA320 User Manual

Page 17: Iecex certification -11, Warning

Advertising
background image

<2. Notes on Handling>

2-

IM 01C50B01-01E

2.7.4 TIIS Certification

a) TIIS Flameproof Type
The model YTA /JF3 temperature transmitter, which

has obtained certification according to technical

criteria for explosion-protected construction of

electric machinery and equipment (Standards

Notification No.556 from the Japanese Ministry of

Labor) conforming to IEC standards, is designed

for hazardous areas where explosive gases and/or

inflammable vapors may be present. (This allows

installation in Division 1 and 2 areas) To preserve

the safety of flameproof equipment requires

great care during mounting, wiring, and piping.

Safety requirements also place restrictions on

maintenance and repair activities. Users absolutely

must read “Installation and Operating Precautions

for TIIS Flameproof Equipment” at the end of this

manual.

WARNING

The terminal cover should not be opened at least

for three minutes after the power is turned off.

The terminal section of the flameproof YTA

series is made of resin-filled, explosion-

protected construction. The technical standards

for this flameproof construction require that

the possibility of explosion resulting from a

prospective short-circuit current*

1

of up to 4000

A be prevented even for cases when external

power supply circuits are short-circuited

accidentally.

Install a fuse or a circuit breaker having a

breaking capacity of at least 4000 A in the higher-

order power line connected to the YTA series.

The breaking capacity refers to the upper limit

of current that can be cut off. Normally, a fuse

or a circuit breaker having a breaking capacity

of greater than 5000 A is used in power supply

circuits. Confirm that this is true with your factory.

No extra measures need be taken after the

confirmation.

Note that the rated current of the YTA series in

terms of explosion protection is 4 to 20 mA; keep

the input current of the YTA series within the

appropriate range.

*1:

Refers to a current that flows when a fuse in a circuit is

substituted with a connecting metal piece having virtually

no impedance and the circuit is then shorted. For AC

circuits, this current is represented by a root-mean-square

value (JIS C6575).

2.7.5 IECEx Certification

a) IECEx Intrinsic safety “ia”
Caution for IECEx Intrinsic safety “ia”.

Note 1. Model YTA110/SU2, YTA310/SU2, and

YTA320/SU2 temperature transmitters are

applicable for use in hazardous locations:

• No. Certificate: IECEx KEM 09.0032X

• Applicable standard: IEC60079-11:2011,

IEC60079-0:2011, IEC60079-26:2006

• Type of Protection and Marking Code:

Ex ia IIC T4...T5 Ga

• Ambient Temperature:

-40 to 70°C for T4, -40 to 50°C for T5

• Enclosure: IP67

Note 2. Electrical Data

• [Supply circuit (Terminals: + and –)]

Ui = 30 V, Ii = 165 mA, Pi = 900 mW

Effective internal capacitance, Ci = 20 nF

Effective internal inductance, Li = 730 μH

• [Sensor circuit (Terminals: 1 to 5)]

Uo = 9 V Io = 40 mA Po = 90 mW

Max. allowed external capacitance, Co = 0.7 μF

Max. allowed external inductance, Lo = 10 mH

Note 3. Installation

• All wiring shall comply with local installation

requirements. (Refer to the installation diagram)

Note 4. Operation

• Keep strictly the “WARNING” on the label on

the transmitter.

WARNING: POTENTIAL ELECTROSTATIC

CHARGING HAZARD. SEE

USER’S MANUAL BEFORE USE.

Note 5. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void IECEx

Certification.

Note 6. Conditions of Certification

• Because the enclosure of the Temperature

Transmitter is made of aluminium, if it is mounted

in zone 0, it must be installed such, that, even in

the event of rare incidents, ignition sources due

to impact and friction sparks are excluded.

• Avoid any actions that cause the generation of

electrostatic charge on the non-metallic parts,

such as rubbing with a dry cloth on coating face

of product.

Advertising