<8. Setting Parameters>

8-2

IM 01C27B01-01EN

Table 8.1

Parameter Usage and Selection

Item

Description

Tag No

Sets the tag No. as Device Tag (Software Tag). Sixteen characters

(alphanumeric characters, including - and •) can be set.

Output

The process variable and the diagnostic result can be output.
Either or all of differential pressure/pressure (AI1:Process Value), static

pressure (AI2:Process Value), temperature(AI3:Process Value) of capsule

or amplifier and self-diagnostic information (UAPMO:Diagnostic Status)

can be set to the output

Range

Adjust the range corresponding for 0% to 100%.
The unit of the range, input value at 0% (LRV) and input value at 100%

(URV) is set.

Note: LRV and URV can be set within the range of -32000 to 32000.

Damping time constant

Damping time constant is used to reduce the large fluctuation of pressure

signal and given by each Process Value Filter Time parameter for

differential Pressure/pressure (AI1) and Static pressure (AI2).

Output signal and integral indicator mode

Sets mode for output signal and integral indicator to “linear mode”

(proportional to input differential pressure) or to “Square root mode”

(proportional to flow).

Output signal low cut mode

Used mainly to stabilize output near 0 if output signal is the square root

mode. Two modes are available: forcing output to 0% for input below a

specific value, or changing to proportional output for input below a specific

value.

Integral indicator range of scale and unit

Sets one of differential pressure/pressure value, static pressure value, or

temperature value for the integral indicator scale.

Note: LRV and URV can be set within the range of -32000 to 32000.

Unit for displayed temperature

Sets a temperature unit to be displayed.

Unit for displayed static pressure

Sets a pressure unit for the static pressure to be displayed

Direction of impulse piping connection

(which is high pressure, L side or R side)

Used where installation conditions makes it imperative to connect high

pressure side impulse line to low pressure side of transmitter.
Normally, correspond by replacing impulse line, and use this function only

when unavoidable.

Range with actual input applied

Range corresponding for 0% to 100% signal is set with actual input

applied.
The output setting can be done just 100% to user’s reference pressure

output.
However, when shipping it, the calibration is done in high accuracy as for

DPharp. Please do the span setting by a usual range setting.

Zero Point Adjustment and Span Adjustment Handle Zero Point Adjustment and Span Adjustment.

There are two methods of Zero Point Adjustment, using external zero-

adjustment screw and using the device configuration tool.

Reset adjustment

The amount of the adjustment set by user can be cleared.

Software write protect

Prohibit writing the setting data.

Operational mode

Set the operational mode of the sensor and integral indicator, etc.

Note: Some of the parameter settings are in the dialogue form called method, the on-line instructions you can configure the parameters

easily.

8.3.2 Function Block and Menu Tree

(1) Function Block
The function of this transmitter is shown below.

A specific function might not be able to be used

according to the field wireless configuration tool

used. When the field wireless configuration tool

of our recommendation is used, the software

attached to the Field Wireless Integrated Gateway is

necessary for setting the dotted line part.

Refer to Subsection 9.2 “Calibration Instruments

Selection” for the field wireless configuration tool of

our recommendation.