<8. Setting Parameters>

8-23

IM 01C27B01-01EN

(4) Reset Adjustment
Reset Adjustment clear the amount of adjustment.

Reset Ajustment can be performed using CAL_

CLEAR of the differential pressure (AI1 block) Cal

Cmd parameter for the input pressure and using

CAL_CLEAR of the static pressure (AI2 block) Cal

Cmd parameter for the static pressure. After Reset

Adjustment, confirm the status by using Cal Status

of the cleared block. The amount of adjustment

made by the external zero-adjustment screw can be

reset to the initial setting as well.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block: Cal Cmd: CAL_CLEAR

AI2 block: Cal Cmd: CAL_CLEAR

8.3.15 Software Write Protect

Hardware write protection and software write

protection functions are available for this

transmitter.

• Procedure to call up the protection setting

parameter (UAP Option)

UAPMO block: UAP Option
The following settings can be configured in the

UAP Option parameter.

- Setting to enable or disable software write

protection.

- Setting to enable or disable the hardware

write protection switch.

- Setting to enable or disable changing

the setting to the Diagnostic Switch and

Diagnostic Configuration parameters.

• Procedure to call up the protection setting

display parameter (Hardware Write Protect)

UAPMO block: Hardware Write Protect
The Hardware Write Protect parameter enables

the switch status of hardware write protection to

be displayed.

For the relationship between hardware write

protection and software write protection, refer to

section 10. “Parameter Summary.”

8.3.16 Switching to Deep Sleep Mode

When the instrument will not be used for a long

time, switch the instrument to deep sleep mode to

conserve battery power. To switch to deep sleep

mode, follow the procedure below.

• Procedure to call up the switch-to-deep-sleep

parameter

TRANSDUCER block: Special Cmd

Set Deep Sleep mode(Standby) to the Special

Cmd parameter for the TRANSDUCER

block. To start from deep sleep mode, either

remove and insert the battery pack, or using

the provisioning device tool or the device

configuration tool via infrared communication.

CAUTION

After setting the deep sleep mode by infrared

device configuration tool, keep the infrared port

of device away from any other infrared signals.

NOTE

• Transmitter becomes the stop state after

setting deep sleep mode and cannot reply

any request from the device configuration

tool via wireless communication.

• For this reason, there is the case that an

error is display on the device configuration

tool via wireless communication.

• To wake up from deep sleep mode, please

pull battery pack and wait more than 30

seconds before attaching battery pack.

8.3.17 Switching to Silence Mode

This is a function to pause the instrument when

it cannot join the field wireless network after a

specified time has elapsed. This function is effective

in conserving battery power when, for example, the

installation of the field wireless integrated gateway

is delayed compared to that of field wireless

devices. The default value is 28800 seconds (8

hours). Thereafter, a cycle of a one-hour pause and

six-minute search is repeated until the instrument

can join the field wireless network.

• Procedure to call up the switch-to-silence

parameter (Radio Silence)

UAPMO block: Radio Silence
Set 0 to 2

31

seconds for the Radio Silence

parameter of the UAPMO block. If 0 is set, the

Radio Silence parameter is invalid. To start from

deep sleep mode, either remove and insert the

battery pack, or use the provisioning device

tool or device configuration tool via infrared

communication.