A7-9

IM 01S01C01-01EN

Q3. On a segment where an FVX110 works

as the LAS, another device cannot be

connected. How come?

A3-1. Check the following bus parameters that

indicate the bus parameter as being the

LAS for the FVX110 and the capabilities of

being the LAS for the device that cannot be

connected:

• V(ST), V(MID), V(MRD) of FVX110:

ConfiguredLinkSettingsRecord (index 385)

• V(ST), V(MID), V(MRD) of problematic

device: DlmeBasicInfo

Then, confirm that the following conditions

are met:

FVX110

Problematic

Device

V(ST)

>

V(ST)

V(MID)

>

V(MID)

V(MRD)

>

V(MRD)

A3-2. Check the node address of the problematic

device is not included in the V(FUN)+V(NUN)

of the FVX110.

Advertising