<13. General Specifications>

13-1

IM 01S01C01-01EN

13. General Specifications

13.1 Functional Specifications

Functional specifications for Fieldbus

communication conform to the standard

specifications (H1) of F

OUNDATION

fieldbus.

Supply Voltage

9 to 32 V DC for general use, flame proof type,

Type n, or nonincendive.

9 to 24 V DC for intrinsically safe type Entity model

9 to 17.5 V DC for intrinsically safe type FISCO

model

Communication Requirements

Supply Voltage: 9 to 32 V DC

Current consumption:

Steady condition: 15 mA (max)

Software download condition: 24 mA (max)

Ambient Temperature Limits

-20 to 70°C (-4 to 158°F)

Ambient Humidity Limits

0 to 100 %RH

LCD Display

84 column x 32 lines full-dot matrix with LED

backlight.

3 lines indication as

• Top line

14 alphanumerics indication of main description

(Main Tag) such as PD TAG of field device.

Scroll up to maximum 32 alphanumerics

• Middle line

5 digits process value including +/- sign and unit

of 5digits x 2 lines

• Bottom line

14 alphanumerics of communication status and

indicate description (Sub Tag) such as block

information.

Bar graph, Scroll bar, Page information, Scroll

direction information, Squawk

Process value

(Middle line)

Top line

Unit

(Middle line)

Bottom line

14 characters

14 characters

5 digits

5 digits
5 digits

F1301.ai

Display Scroll Functions

Single scroll and cyclic scroll (Scan mode)

Display up to 16 variables

EMC Conformity Standard:

EN61326-1 Class A, Table 2

(For use in industrial location)

Link Master Function:

Link Master function is supported.

Function Block:

Block name

Number

Execution time

Note

MAO

2

30 ms

Output eight analog signals from field deveces

IS

2

30 ms

Input Selector block provides selection of up to eight inputsand generate

an output based on the configured action

AR

2

30 ms

Arithmetic block permits simple use of popular measurement math func-

tion

PID

2

45 ms

Works as a field controller in conjunction with another function block.

SC

1

30 ms

An output of Signal Characterizer block is a nonlinear function of the

respective input. The function is determined by a table

IT

1

30 ms

Integrator block integrates a variable as a function of the time or accumu-

lates the counts