2 actuator wizard, Actuator wizard -2 – Yokogawa YVP20S User Manual

Page 71

Advertising
background image

8-2

<Toc> <Ind>

<8. SETUP WIZARD>

IM 21B04C50-01E

8.2

Actuator Wizard

Figure 8.2 Actuator Wizard

In the actuator setup menu select the valve action, actuator type, relay type, and valve type.

Then, click Next to begin calibration and tuning.

NOTE

If “linear” is incorrectly selected (when the valve is rotary), there will be large angle span
error message. To correct this, you must use the Configuration Services- Actuator dialog
followed by the Calibration Services- Tuning dialog.

NOTE

Supply pressure must not exceed the Actuator pressure rating marked on the actuator.
Positioner supply pressure should be at least 35 kPa higher than the upper spring range of
the valve.