3.2

Detaled Descrpton of Functons

Communcaton Port

The communications ports available to GateMODBUS are the COM1–COM9 serial

(RS-232) ports the Ether1 to Ether16 Ethernet ports. The following items are specified in

the Serial Setting tab.

Seral port settng

• Baud rate (4800, 9600, 19200, or 38400 bps)

• Parity (None, Even, or Odd)

Ethernet port settng

• IP address or host name

• Password

Note

The Modbus protocol’s RTU (remote terminal unit) mode prescribes stop bit 2 for no parity, and

stop bit 1 for odd or even parity.

Modbus Communcatons

GateMODBUS supports communications using the Modbus/RTU (serial) and Modbus/

TCP (Ethernet) protocols. The functions and registers used by GateMODBUS for data

logging are as follows:

Functon

03

04

Description

Read holding register

Read input register

Register numbers that can be loaded:

40001–49999

400001–465535

30001–39999

300001–365535

Also, you can execute the following functions on the configurator to display the

connection status with Modbus devices.

Function

08

Sub-function

00

Description

Loop back test

Note

GateMODBUS does not support the Modbus protocol’s Modbus/ASCII mode.