You can assign names to groups. Names can contain up to 30 alphanumeric characters.

The group names specified here are the default values when Remote Monitor is

connected to GateMODBUS.

Acqurng Data at Fxed Intervals

Using GateMODBUS, data can be acquired concurrently on each port. Therefore

data is logged more efficiently when connecting each Modbus device to a separate

port rather than connecting several Modbus devices to a single port. Also, registers

occurring in a continuous sequence on 1 instrument are read all at once. Therefore, the

more sequentially continuous registers there are, the more efficiently data is acquired.

However, if a register within the sequence experiences an error, the error applies to all

registers in the sequence.

For example, given the three registers below, TAG001–TAG003 are read all at once at

each scan interval.

Tag

COM Port

Modbus Address

Regster numbers read

TAG001

COM1

1

30001

TAG002

COM1

1

30002

TAG003

COM1

1

30003

Data Dropout

If data is being read at the timing shown below, data is dropped. Data dropout can occur

in the following circumstances.

• If the tme requred to read the tags s longer than the scan nterval
In the figure below, by the time the tags at T1 have been read, T2 has already passed

and T3 begins. Therefore, the tags to have been read at T2 were dropped.

TAG001 TAG002 TAG003 TAG004 TAG001 TAG002 TAG003 TAG004

T

T1 = T +

t

T2 = T +

t x 2

T3 = T +

t x 3

Interval:

T

Data reading at time T

Data reading at time T1

Time

Data

dropout

occurs

Time

Timing of Data Reading

3.2 Detaled Descrpton of Functons