Function, Command/response (for normal operation), Example – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 32

Advertising
background image

3-18

<Toc> <Ind>

<3. PC Link Communication >

IM 77J04J11-01E 1st Edition : 2006.08.25-00

WRM Monitors D registers and I relays on a word-by-word basis

Function

Reads the register data that have been specified in advance by the WRS command.

Before executing this command, the WRS command must always be executed to
specify which registers are to be monitored. If no register has been specified, error
code 06 is generated.

For the format of response in the event of failure, see subsection 3.1.2.

The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.

Command/Response (for normal operation)

Number of Bytes

1

2

2

1

3

2

1

1

Number of Bytes

• • •

1

2

2

2

4

4

4

2

1

1

Command

element

STX

Address

number

(ADR)

CPU

number

01

Checksum

0

WRM

ETX

CR

Response

element

STX

OK

dddd1

dddd2

ETX

CR

Address

number

(ADR)

CPU

number

01

• • •

ddddn

Checksum

The response is returned in a 4-digit character string (0000 to FFFF) in hexadecimal.

ddddn: read data of the number of words specified by the WRS command

ddddn is a character string in hexadecimal.

n=1 to 32

Example:

Monitoring the alarm-1 setpoint (D0101) and alarm-2 setpoint (D0102) of the M Series with
address number 01.

(This command reads the registers specified by the WRS command.)

[Command]

[STX]01010WRME8[ETX][CR]

CPU number: 01

The alarm-1 setpoint 500 (01F4 [HEX]) and alarm-2 setpoint 500 (01F4 [HEX]) are re-
turned with respect to the above command (50.0 is expressed as 500).

[Response]

[STX]0101OK01F401F412[ETX][CR]