Modbus communication, 1 overview – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 47

Advertising
background image

<Toc> <Ind>

<5. MODBUS Communication >

5-1

IM 77J04J11-01E 1st Edition : 2006.08.25-00

5.

MODBUS Communication

5.1

Overview

The use of MODBUS communication enables the M Series to communicate with a
PC. In this communication, you can use a PC to read/write data from/into D registers,
which are internal registers of the M Series.

PC

A maximum of 1200 m; up to 31 slave stations

Figure 5-1 Example of Connection for MODBUS Communication

Hereafter, PCs are generically called "higher-level devices."

See Also

Chapter 6 for information on the D registers.

For the MODBUS communication of the M Series, two transmission modes are supported:
ASCII mode and RTU mode (binary system).

Table 5-1

ASCII and RTU Modes

Item

ASCII Mode

RTU Mode

Number of data bits

7 bits (ASCII)

8 bits (binary)

: (colon)

Not necessary

Message end mark

Message start mark

CR+LF

Not necessary

Message length (*1)

Error detection

2N+1

N

Data time intervals

1 second or less

24 bit time or less (*2)

Longitudinal redundancy check: LRC Cyclic redundancy check: CRC-16

*1:

When the message length in the RTU mode is assumed to be "N."

*2:

When the baud rate is 9600 bps, 1

Ϭ

9600

ϫ

24 seconds or less applies.

In MODBUS communication, a higher-level device identifies each M Series with an ad-
dress number, which ranges from 01 to 99.