Sterling RT User Manual

Page 22

Advertising
background image

– 22 –

Chart 6 - Troubleshooting

SYMPTOMS

A. Gas odor.

B. Delayed ignition.

C. Pilot will not light, or will not
stay

lit.

D. Main burners will not light.

POSSIBLE CAUSES

1. Shut off gas supply immedi-
ately.
2. Blocked heat exchanger.

3. Drafts around heater.

4. Negative pressure in the
building.
5. Blocked draft hood/fl ue
collector.

1. Excessive primary air.

2. Main burner ports clogged
near

pilot.

3. Pressure regulator set too low.

4. Pilot decreases in size when
main burners come on.
5. Pilot fl ame too small.

1. Main gas off.
2. Pilot adjustment screw turned

too low on combination main

gas

valve.

3. Air in gas line.
4. Dirt in pilot orifi ce.

5. Extremely high or low gas
pressure.
6. Pilot valve not opening.

a. Faulty wiring.

b. Defective ignition control.

c. Defective valve.

7. No spark.

a. Faulty wiring.

b. Defective pilot.

c. Defective ignition control.

d. Sensor grounded.

1. Main gas off.
2. Lack of power at unit.

3. Thermostat not calling for heat.
4. Defective limit switch.

5. Improper thermostat or trans-

former wiring at gas valve.

6. Defective gas valve.
7. Defective thermostat.

CORRECTIVE ACTIONS

1. Inspect all gas piping and
repair.
2. Clean heat exchanger.

3. Eliminate Drafts. Refer to

installation.
4. See installation.

5. Clean draft hood/fl ue collector.

1. Close air shutter. Refer to
operation.
2. Clean main burner ports.

3. Reset manifold pressure.

Refer to operation.

4. Supply piping is inadequately

sized. Refer to installation.

5. Clean pilot orifi ce. Refer to
operation.

1. Open all manual gas valves.
2. Increase size of pilot fl ame.

3. Purge air from gas supply.
4. Remove pilot orifi ce. Clean

with compressed air or solvent.

(Do not ream).

5. Refer to operation.

6.

a. Inspect & correct all wiring.

b.

Replace

c.

Replace.

7.

a. Inspect & correct all wiring.

b.

Replace.

c.

Replace.

d. Inspect & correct ignition

system.

1. Open all manual gas valves.
2. Replace fuse or turn on power
supply.
3. Turn up thermostat.
4. Check limit switch with
continuity tester. If open,
replace limit switch.
5. Check wiring per diagrams.

6. Replace gas valve.
7. Check thermostat and replace
if

defective.

Advertising