Performance and specification data, Evaporative cooling units figure 1 – Sterling EV User Manual

Page 3

Advertising
background image

3

4"

(102)

8" CELdek®
(Optional 12")

2" CELdek®

Overflow

Pump

Ball
Valve

1/4" Water
Inlet

Float Valve

Bleed-off

Water
Distribution
Assembly

“A”

Intake
Filter

S

S

SECTION S-S

3/4" NPT

Drain

(Capped)

Junction Box

Liquid Tight
Electrical
Tubing

43"

(1092)

36"

(914)

PERFORMANCE AND SPECIFICATION DATA

Evaporative Cooling Units

Figure 1

200

0.5

100%

90%

80%

70%

60%

0.4

0.3

0.2

0.1

Air Velocity - FPM

Evaporative Cooling Efficiency

Air Pressure Drop Inches - WG

300

400

500

600

700

800

12"

8"

8"

12"

Evaporative Cooling Efficiency

Air Pressure Drop

CELdek® EVAPORATIVE MEDIA
The Evaporative Cooler utilizes high effi ciency
CELdek® media. CELdek® is made from a special
cellulose paper, impregnated with insoluble anti-
rot salts and rigidifying saturants. The cross fl uted
design of the pads induces highly-turbulent mixing
of air and water for optimum heat and moisture
transfer. The evaporative coolers are available
with standard 8 or optional 12 inch media which
produce high effi ciency and high face velocities,
along with a 2" distribution pad to disperse the
water evenly over the pads.

Figure 2

8" Saturation 12" Saturation

8" or 12" Media

Pressure Drop

“A” Unit Shipping

Operating

CFM

Effi ciency

Effi ciency

Face Area

Size

in W.C.

Width

Wt.

Wt.

(cu. m/s) (cu. m/s)

Range

Range

Ft.

2

in. (kPa)

(kPa)

in. lb. lb.

*Capacity

MIN.

MAX. MIN. MAX. MIN. MAX.

(m

2

) (mm) MIN.

MAX.

(mm) (kg) (kg)

10,15

800 4,500 78 88 89 92 7.01

31

x

32-9/16 0.03 0.23

32-3/4 137

301

(0.378)

(2.124)

(0.65)

(787

x

827)

(0.01)

(0.06)

(832)

(62) (136)

20, 25, 50

1,600

5,500

77

88

88

92

9.38

31 x 43-9/16

0.03

0.20

43-3/4

166

386

(0.755)

(2.596)

(0.87)

(787

x

1106)

(0.01)

(0.05)

(1111)

(75) (175)

30, 35, 60, 70

2,400

8,500

77

86

88

92

11.75

31 x 54-9/16

0.05

0.30

54-3/4

192

468

(1.133)

(4.012)

(1.09)

(787

x

1386)

(0.01)

(0.07)

(1391)

(87) (212))

40,

80

3,200 8,500 77 86 87 92 12.92 31

x

60 0.07 0.28

60-1/4 206

509

(1.510)

(4.012)

(1.20)

(787

x

1524)

(0.02)

(0.07)

(1530)

(93) (231)

*Capacities - (50, 60, 70 and 80) are for Dual Furnace Unit Types only.

Performance and Dimensional Data

Table 1 (Refer to individual unit submittals for more specifi cations.)

A

32-7/8"

(835)

43-7/8"

(1114)

54-7/8"

(1394)

60-3/8"

(1534)

Capacity

10/15

20/25/50

30/35

60/70

40/80

Advertising