If a cooling coil is installed in the warm air plenum a

minimum distance of 3" or 7" is required between

the top of the cooling coil and the add-on heater

(depending from which side of the plenum

the add-on heater is inserted). (Please see Fig. 4)

In both cases, a minimum distance of 2" must be

kept between the top of the add-on heater

and the elbow, Tee or plenum-end take off

of the main supply duct.

The heater may be installed on any available side of the

plenum. An installation and service clearance of 28 inches is

required from the heater control box to a wall, partition or any

other obstruction.

If the heater is installed on the same side as the flue pipe a

minimum clearance of 10 inches must be maintained between

the flue pipe and the heater control box. (Please see Fig. 5)

Select the plenum side, which offers the most space for

installation and service.

VERY IMPORTANT

BAFFLES MUST ASSURE MAXIMUM AIR FLOW OVER THE HEATING ELEMENTS.

- Screw the baffles to bottom flanges of casing, as shown in Fig. 6.

- Cut baffles to size allowing only 1/8" clearance for insertion of heater.

AIR FLOW

All the air from the furnace must pass through the heater element. If the heater element casing is smaller than the

plenum the space between the plenum and the element casing must be blocked off with baffles. (Please see Fig. 7)