Thermolec Standard Boiler User Manual

Page 3

Advertising
background image

Page 1

Installation Guidelines for Thermolec Electric Boilers Model B

1 Important

1.1

These instructions should be used as a general guide only. Electrical Code and local utility requirements must

be followed and take precedence over these instructions.

1.2

Thermolec electric boilers are manufactured with quality components for maximum life, durability and

minimum service. To ensure a satisfactory installation it is imperative that you read these instructions

carefully before installing and operating the heating system.

Failure to do so may result in breach of warranty.

2 Unpacking

2.1

Inspect the unit and check whether there are missing parts.

2.2

Report any damage or claims to the carrier immediately.

2.3

For all returns to be accepted they must be authorized by the manufacturer.

3

Location and dimensions

3.1

These boilers are designed for wall mounting. Please see Table 1 below for overall dimensions.

Table 1 also gives the minimum clearances to combustible material as well as recommended distances for

ease of service (e.g. replacement of tubular elements).

3.2

The boiler room should be well ventilated as to maintain the temperature below 25°C (77°F).

3.3

The unit must be mounted level on a vertical wall with the outlet fitting on the left side of the unit.

Table 1

Models

Width Height Depth

Front

Back

Top

Right Others

Short Models

up to 23 kW 1ph

up to 18 kW 3ph

Long Models

up to 40 kW

TMB

12"

12"

36"

0"

24"

6"

12"

36"

0"

12"

6"

36"

0"

12"

6"

Overall dimensions

Clearances

Dimensions and Clearances

18"

18"

9-1/2"

13"

18"

9"

18"

28"

9-1/2"

Advertising