Thermolec Standard Boiler User Manual

Page 6

Advertising
background image

Page 4

6.2

In order to ensure an adequate flow rate :

6.21

Pressure loss (referred as "Head") caused by water friction in the system should not exceed the

capacity of the pump.

6.22

Please refer to Table 5 below to find the copper pipe diameter (type L) recommended to

accommodate the water flow found in Table 4 above.

6.23

Elbows and valves will greatly add to the head loss in the system. An appropriate water flow rate

must be maintained to avoid tripping of the temperature limiter. Pipes with diameters larger than

specified in Table 5 will not help to increase water flow.

6.3

The installation must have a drain valve, an expansion tank, maintenance valves and an automatic

pressure reducing fill valve set at 15 PSI (104 kPA). A "T" fitting (1-1/4" NPT) must be installed at the

supply outlet of the unit. This "T" must be equipped with a reducing bushing 1-1/4" to 3/4" NPT, facing

upwards, to accept a 3/4" NPT pressure relief valve. This safety valve must be installed vertically. Except

for the pressure relief valve, the above plumbing supplies are not supplied with the unit. Please refer to

illustrations A, B and C at the end of this manual.

Table 4

Table 5

6

Water circulation and plumbing notes

6.1

The system is designed to operate with a maximum output temperature of 180°F or

lower and a temperature rise across the unit of 20°F or lower.

Please refer to Table 4 for the recommended flow rate versus the capacity of the boiler.

Pipe Diameter

Imp. Gallons / min

US Gallons / min

(Type L Copper)

3.6

4.3

3/4"

8.4

10.1

1"

14.4

17.3

1-1/4"

Maximum Flow Rate

Maximum Flow Rate @ 15 psi

Capacity (kW)

Imp. Gallons / min

US Gallons / min

3

0.9

1.1

5

1.5

2.0

6

1.7

2.0

8

2.3

2.8

9

2.6

3.1

10

2.9

3.5

11

3.2

3.9

12

3.5

4.2

15

4.4

5.3

18

5.2

6.2

20

5.8

7.0

23

6.7

8.0

25

7.3

8.8

30

8.7

10.4

35

10.2

12.2

36

10.4

12.5

40

11.6

13.9

42

12.2

14.6

Recommended Water Flow Rate vs Capacity

Advertising