Stuart Turner RGFL4000 User Manual

Page 4

Advertising
background image

- 4 -

Cont ...

1 READ BEFORE COMMENCING PUMP INSTALLATION

A.

Water storage capacity.
1.11 The water storage capacity (must be a minimum of 230 litres) and be sufficient to

meet the flow rates required by the pumped equipment and any other water using

fittings and appliances, which may be operated simultaneously.

1.12

Ensure the pump is primed as described in the priming section before starting,

damage to the shaft seal will result otherwise. See Section 5 - Commissioning.

B.

Water temperature
The water entering the pump must be controlled as follows:
1.13 The maximum allowable water temperature is 80

o

C (65

o

C for KFL models).

1.14 The minimum allowable water temperature is 4

o

C.

1.15

DO NOT fit a pump if the hot water is heated via a method whereby the water

temperature cannot be controlled, such as solar or solid fuel

you must consult the

pump assist team at Stuart Turner Ltd.

C.

Water flow
1.16 For this pump to operate correctly there must be a minimum gravity flow of at

least 0.6 l/min (1 l/min for KFL models) through all outlets to be pumped.

D.

Pipework - General
1.17

Secure pipework: Ensure pipework to and from pump is independently

supported & clipped to prevent forces being transferred to inlet and outlet

branches of pump.

1.18

Flux: Solder joints must be completed and flux residues removed prior to pump

installation

(flux damage will void any warranty).

1.19

Pipework design: Care should be taken in the design of pipework runs to

minimize the risk of air locks e.g. use drawn bends rather than 90

o

bends.

1.20

DO

NOT introduce solder flux to flexible hoses, pumps or pump parts

manufactured from plastic.

1.21

DO

NOT allow contact with oil or cellulose based paints, paint thinners or

strippers, acid based descalents or aggressive cleaning agents.

1.22

DO

NOT install a non-return valve, or devices which contain non-return

valves, in the suction (inlet) pipework to the pump. The pump must be free

to vent to the supply tank at all times.

1.23

DO

NOT bend the flexible hoses beyond 30

o

. They must be installed as

straight as possible.

1.24

DO NOT connect this pump to the mains water supply.

E.

Plumbing & Electrical Installation Regulations
1.25 The plumbing installation must comply with “The Water Supply (Water Fittings)

Regulations 1999” and “BS 6700” building regulations.

1.26 The plumbing installation must be installed by a qualified person.
1.27 The electrical installation must be carried out in accordance with the current

national electrical regulations.

1.28 The electrical installation must be installed by a qualified person.