Performance review - light derating factor, Caution – STI 6700 User Manual

Page 2

Advertising
background image

• This enclosure is rated to protect signaling appliances indoors and in areas of indirect weather

exposure. The cover may be used outdoors only with devices also suitable for outdoor use.

• When covering fire-signaling appliances with this enclosure, some light and sound loss

occurs. Please follow these guidelines listed during installation.

• Voice speaker appliance: No spacing adjustment is required for 0.5W, 1.0W and 2.0W

appliances.

• Refer to the appliance manufacturer's candela rating. Multiply this number by the light loss

value from the chart below to determine the new candela rating. Use this number and refer
to the notification layout table of NFPA 72 for proper device locations.

• The use of this cover on audible devices decreases the sound output by 6dB(A). Actual sound

level output should be checked after installation to determine if adequate sound levels exist.
Refer to the notification layout table of NFPA 72 for proper device locations.

Performance Review - LIGHT DERATING FACTOR

ADT SECURITY

ADTG1-V SERIES

40%

34%

HONEYWELL

XLS202 SERIES

40%

34%

AMSECO

SL24W-153075

22%

37%

HONEYWELL

XLSG1-HV SERIES

40%

34%

AMSECO – COLORED LENSES

SL24W-153075 A, B, G, OR R

47%

26%

HONEYWELL

XLSG1-HOV SERIES

40%

34%

AMSECO – COLORED LENSES

SL24C-3075110 A, B, G, OR R

47%

26%

MIRCOM

FS-240

47%

26%

AMSECO – COLORED LENSES

CSL24W-A, B, G, OR R

47%

26%

MIRCOM

MS SERIES

43%

45%

AMSECO – COLORED LENSES

CSL24C-A, B, G, OR R

47%

26%

MIRCOM

MG1-V SERIES

40%

34%

DETECTION SYSTEMS

GES24 SERIES

-

31%

MIRCOM

MG1-HV SERIES

40%

34%

DETECTION SYSTEMS

GES24-15/75

-

-

MIRCOM

MG1-HOV SERIES

40%

34%

EST / EDWARDS

2440S SERIES

43%

45%

MIRTONE

MG1-V SERIES

43%

45%

EST / EDWARDS

202 SERIES

43%

45%

NATIONAL TIME & SIGNAL

GES24 SERIES

-

31%

EST / EDWARDS

G1-V SERIES

40%

34%

NATIONAL TIME & SIGNAL

GES24-15/75

-

-

EST / EDWARDS

G1-HV SERIES

40%

34%

POTTER ELECTRIC

AS-24-153075R

47%

26%

EST / EDWARDS

G1-HOV SERIES

40%

34%

POTTER ELECTRIC

AS-24-153075W

47%

26%

EST / EDWARDS

EG1-V SERIES

40%

34%

SECUTRON

GES24 SERIES

-

31%

EST / EDWARDS

EG1-HV SERIES

40%

34%

SECUTRON

GES24-15/75

-

-

EST / EDWARDS

EG1-HOV SERIES

40%

34%

SIEMENS

202- SERIES

43%

45%

FARADAY LLC

2700

-

57%

SIEMENS

G1-V SERIES

40%

34%

GENTEX

GES24 SERIES

-

31%

SIEMENS

U-MCS SERIES

-

-

GENTEX

GES24-15/75

-

-

SYSTEM SENSOR

SS24110ADA

46%

37%

HARRINGTON SIGNAL

GES24 SERIES

-

31%

SYSTEM SENSOR

P2, PC2, P4, PC4, SX, SC

53%

61%

HARRINGTON SIGNAL

GES24-15/75

-

-

WHEELOCK

RSS-24MCW

-

-

HONEYWELL

XLSG1-V SERIES

43%

45%

ZITON PTY LTD

ZG1-V SERIES

40%

34%

MANUFACTURER

SERIES

STI-1210

STI-1221/1221A4X

MANUFACTURER

SERIES

STI-1210

STI-1221/1221A4X

STI-1210 Series Sound Derating Factor

System Sensor P2, PC2, P4, PC4, SX, SC series models: 6.7 dBA

General: 6 dBA

STI Generic Light Loss Value

STI-1210 Series: 53%; STI-1221 Series: 61%

SAFETY TECHNOLOGY INTERNATIONAL, INC. • 2306 AIRPORT ROAD • WATERFORD • MICHIGAN 48327-1209 • PHONE: 248-673-9898 • FAX: 248-673-1246 • INFO @ www.sti-usa.com

UL INSTALLATION REQUIREMENTS

STI-1210 / STI-1221 SERIES

04/2006

CAUTION: