Dip switch settings, Programmable features – STI AP-1-G-I User Manual

Page 3

Advertising
background image

- 3 -

Integral Sounder Tones (DIP Switch No. SW1-SW3)

The Alert Point Lite has seven different selectable alarm tones ranging from 95 to 102dB.

Sounder Timer Options (DIP Switch No. SW5 & SW6)

Four alarm conditions are available and can be selected by changing the DIP switch settings. These are:
30 seconds, 3 minutes, 20 minutes or continuous.
If any duration other than “continuous” is used, the alarm will silence after the selected time has elapsed.

This alarm will NOT be able to be reactivated until the unit is reset with the reset key.

Key Switch – Reset (DIP Switch No. SW7)

This allows the user greater control if misuse becomes a major factor.

SW7 position - ON: The Alert Point Lite will fully reset after activation when using the reset key.
SW7 position - OFF: Even if the Alert Point Lite is reset after activation using the reset key, all sounders
will continue to run until the unit is reset using the master key switch.

DIP Switch Settings

Important: Changes to any DIP Switch settings will only take effect after the Alert Point Lite has been
reset using the master key switch (turn “OFF” then back “ON”).

FEATURES

DIP SWITCH SETTING

ACTION

Integral
Sounder Alarm
Tone

SW1

SW2

SW3

Tone

Sound Pattern

OFF

OFF

OFF

1

800Hz - 970Hz (Sweep)

ON

OFF

OFF

2

800Hz - 970Hz (Sweep)

OFF

ON

OFF

3

988Hz / 250ms - 645Hz / 250ms (Alternating)

ON

ON

OFF

4

670Hz / 250ms - 845Hz / 370ms (Alternating)

OFF

OFF

ON

5

800Hz - 970Hz in 350ms (Sweep)

ON

OFF

ON

6

2400Hz - 2850Hz in 110ms (Sweep)

OFF

ON

ON

7

2400Hz - 2850Hz in 330ms (Sweep)

ON

ON

ON

8

Not implemented

SW5

SW6

Sounder Duration

OFF

OFF

Sounders run continuously (until manually reset)

ON

OFF

Sounders switch off automatically after 30 seconds

OFF

ON

Sounders switch off automatically after 3 minutes

ON

ON

Sounders switch off automatically after 20 minutes

Alert Point Lite returns to “standby” condition after resetting

with reset key.

Alert Point Lite latches in “alarm” condition until it is

manually reset using the master key switch.

The Alert Point Lite expects to be connected to another Alert

Point Lite, otherwise a warning beep is emitted.

No fault will be indicated if an Alert Point Lite is not connected

to another Alerrt Point Lite, it is not looking for a connection.

SW4 ON

Not used

SW4 OFF

Not used

Sounder
Duration Timer

Reset

Networking
the Alert Point
Lite

Factory setting

SW7 ON

SW7 OFF

SW8 ON

SW8 OFF

Programmable Features

Advertising