Specifications, Fault finding, Warranty – STI AP-1-G-I User Manual

Page 7

Advertising
background image

- 7 -

Specifications


Power source

9V DC battery (included)

Standby current

45µA

Alarm current

28mA (low volume) / 32mA (high volume)

Operating temperature

32° to 120°F (0° to 49°C)

Sounder output (at 1m)

95 – 102dB

Sounder tones

7

Network

>2 units spaced less than 50m apart

Fault Finding

A simple test completed on each individual unit will immediately highlight if any of the following faults are
evident:

Low Battery condition, Network connection loss


Using the master key, turn the unit “OFF” and then back “ON.”

If no audible beeps sound within 5 seconds, the unit has no faults.
If a short single beep sounds within 5 seconds the unit has a low battery fault.
Replace the battery.
If 2 short beeps sound within 5 seconds the unit has a network fault. Check all the network cable

terminations and/or the wiring associated with the input signal to the device.

Warranty

Safety Technology International, Inc. warrants to the original consumer/purchaser what this product shall
be free of defects in material and workmanship under normal use and circumstances for a period of one
(1) year from the original date of purchase.

Electronic warranty form at www.sti-usa.com/wc14.

NETW

ORK IN

NETW

ORK

CO

MMON

NETW

ORK OUT

EXTERNAL SOUNDER
EXTERNAL SOUNDER

+

-

Note:
All external sounders
must be hard-wired
using 2-core cable, and
must have their own
power supply.

It is recommended
that external wiring
does not exceed 50
metres.

VOLUME JUMPER CONNECTION (3 PINS)

DIP SWITCHES

PCB Terminal Diagram