Flashes on cool call, Flashes on heat call – Aprilaire 8344 User Manual

Page 11

Advertising
background image

5. Return the Mode switch to the Off position to stop the heat call.

6. Slide the Mode switch to the Cool position.

7. Use the ADJUST – Down button to lower the temperature 2°- 3° below the

current room temperature. “COOL” on the display will begin to flash and the
cooling equipment should start.

8. MODELS 8348 & 8366 ONLY – Lower the temperature

an additional 2°- 3° and confirm that the second
stage of cooling (Y2) comes on after four (4) minutes.

9. Return the Mode switch to the Off position to stop

the cool call.

MODELS 8346 & 8365 ONLY

10. Slide the Mode switch to the E-Heat position.

11. Use the ADJUST – Up button to raise the temperature 2°-3° above the

current room temperature. The W2 and G terminals will energize,
“E-HEAT” on the display will begin to flash and the heating equipment
should start.

12. Return the Mode switch to the Off position to stop the heat call.