C H A P T E R 3 – C O N F I G U R I N G T H E S O F T W A R E

26

EFM Options: Delta Alarm

Figure 22: EFM Options - Delta Alarm

Field Mill Selector
Select the field mill for which you would like to enable or disable alarms.

Setpoint

Delta Alarm Setpoint is the change of the electric field magnitude required to trigger a Delta Alarm.
For example, with a setpoint of 1 kV/m the Delta Alarm will activate if the field increases or

decreases by 1 kV/m or more within the set interval time.

Interval
Delta Alarm Interval is the time frame that the electric field level needs to change in order to trigger

the Delta Alarm. For example, with an interval of 60 seconds, and a setpoint of 1kV/m, the field

level needs to increase or decrease by 1kV/m or more within 60 seconds to active the Delta Alarm.

Delay

The Delta Alarm Delay is the length of time the field difference must remain higher than the setpoint

before the alarm is activated. If the electric field difference drops below the setpoint before the delay

expires the delay timer will be reset. For example, with a delay of 30 seconds and setpoint of 1 kV/m