Installing a DC power supply

5

FIGURE 22

DC power supply screws

8. Connect the wire to your DC power source, making sure to connect the -48V cable to the

negative terminal on the power supply and the 0V cable to the positive terminal as marked on
the power supply.

The equipment installation must meet NEC/CEC code requirements. Consult local authorities for
regulations.

DANGER

DC return shall be isolated from the chassis ground (DC-I) when connections to the power supply
are made.

CAUTION

To insure adequate bonding when attaching the provided Panduit LCD6-10AF two-hole ground
lug, a minimum of 20 PSI of torque is required to be applied to the mounting hardware used to
attach the ground lug. Use a star washer to ensure an NEBS compliant connection.

1

Chassis attachment screws

2

Assembly screws

1

1

2