Environmental requirements – Brocade VDX 8770-4 QuickStart Guide User Manual

Page 12

Advertising
background image

12 of 32

Brocade VDX 8770-4 QuickStart Guide

Publication Number: 53-1002554-01

CAUTION
For the NEBS-compliant installation of a Brocade VDX 8770-4 with AC or DC systems, use a ground wire
of at least 2 AWG. The ground wire should have an agency-approved crimped connector (provided with
the device) attached to one end, with the other end attached to building ground. The connector must be
crimped with the proper tool, allowing it to be connected to both ground screws on the enclosure. Before
crimping the ground wire into the provided ground lug, ensure that the bare copper wire has been
cleaned and antioxidant is applied to the bare wire.

Environmental requirements

DANGER

Do not install the router in an environment where the operating ambient temperature might
exceed 40°C (104°F).

Table 4

lists the environmental operating ranges for the Brocade VDX 8770-4. The requirements for non-operating

conditions are also provided for acceptable storage and transportation environments.

NOTE

The 0

°

to 40

°

C (32

°

to 104

°

F) range applies to the ambient air temperature at the air intake vents on the left side

(as you face the port side) and port side of the Brocade VDX 8770-4.

The temperature inside the Brocade VDX 8770-4 can be up to 90° C (194

°

F) for some modules during operation.

Cooling policy is based on a combination of ambient temperature and measured temperature on the modules.
Various combinations will result in an increase in fan speed to create more cooling in the switch.
If a component approaches a critical temperature that will trigger a module shutdown, there will be a WARNING
message in the raslog, followed by a CRITICAL message saying that the module will shut down in two minutes.
Use the show environment command to view temperature status.

TABLE 4

Environmental requirements

Condition

Acceptable range during operation

Acceptable range during non-operation

Ambient temperature

0

°

to 40

°

C (32

°

to 104

°

F) outside

switch

-25

°

to +70

°

C (-13

°

to 158

°

F) outside

switch

Humidity

5% to 90% RH noncondensing, at 40

° C

(104

°

F), with maximum gradient of 10%

per hour

10% to 90% RH noncondensing, at 70

°

C

(158

°

F)

Altitude

0 to 3 km (10,000 ft.) above sea level

0 to 12 km (40,000 ft.) above sea level

Shock

20G, 6 ms duration, half-sine wave

33G, 11 ms duration, half-sine wave

Vibration

0.5G p-p, 5-500 Hz at 1.0 octave/minute

2.0G p-p, 5-500 Hz at 1.0 octave/minute

Airflow

Maximum: 675 cu ft/min. (1147 cu
m/hr)
Nominal: 200 cu ft/min. (340 cu m/hr

None required

Maximum heat
dissipation

Up to 6000W or 20,500 BTU/hr

Not applicable

Advertising