Electro-mechanical controllers – Hired-Hand PowerTrak: Connecting Hired-Hand Controllers User Manual

Page 2

Advertising
background image

HIRED-HAND, INC.

· 1733 Co Rd 68 · Bremen, AL 35033 ·-Phone 1-800-642-0123 · Fax 256-287-2000

Manual Part No. 4801-0156 Rev 10/98

Electro-Mechanical Controllers

If you own a PC-OC, PC-SS, PC-D3, PC-DB, PC-LP, PC-OD, PV-TIR, or PC-PH. Your
controller wiring diagram may not match the label inside the controller. The only thing
different is the label. The internal wiring of these controllers did not change. Your
controller will connect to either the 8 wire or the 3 wire PowerTrak. We have put
instructions on the label to wire to either PowerTrak unit. The picture below is the label
you will see for your terminal block.

If you have a 8 wire PowerTrak

Connect to the 9 positions (Ground wire included) labeled with colors.

If you are connecting to a 3 wire PowerTrak

Remove the cordset from the control and remove the fuse wire from the #1 terminal
inside the controller. Connect the two units together using 5 wires. positions 1, 2, 7, 8 and
GROUND. (PT HOT IN connects to HOT OUT(PT), AC NEUT connects to NEUT(PT),
CLOSE connects to CLOSE IN(PT), OPEN connects to OPEN IN(PT), connect ground
from GROUND LUG of PowerTrak to metal plate inside control.)