Operation, 0 operation – Detcon SW-AV1-N4 User Manual

Page 11

Advertising
background image

SW-AV1-N4

SW-AV1-N4 I.M.

Rev. 0.0

Page 7 of 8

3.0 Operation

The SW-AV1-N4 Wireless Alarm Stations provides a strobe and a horn. The wireless alarm station is set to
respond to alarms from the controlling unit via the RXT-320 transceiver. The controller/wireless network has
independent control over the strobes and the Horn, and they will be activated when the appropriate alarm is
activated, via the RL4 Module.

The unit needs to have both the Transceiver and the RL4 configured before the unit will operate properly. To
do this the RL4 Modbus™ address must correspond to the setting of the controller, and the transceiver address
must be set properly for the transceiver to be recognized on the network. Refer to the Controller Manual for
more information.

The horn has up to 32 possible settings, for use in different configurations. The default settings of the horn are
factory set. To change the setting of the horn, remove the rear end of the horn, and set the dip switches
according to the Sound Signals Table.

Table 1 Sound Signals

TONE FREQ/DESCRIPTION

SWITCH

TONE

1

Alt Tones 800/970 Hz at 1/4 sec

11111

2

Sweeping 800/970 Hz at 7Hz

11110

Fast Sweep(LF)

3

Sweeping 800/1000 Hz at 1 Hz

11101

Med Sweep(LF)

4

Continuous at 2850 Hz

11100

5

Sweeping 2400-2850 Hz at 7 Hz

11011

Fast Sweep

6

Sweeping 2400-2850 Hz at 1 Hz

11010

7

Slow Whoop

11001

Slow Whoop

8

Sweep 1200-500 Hz at 1 Hz

11000

Din Tone

9

Alt. Tones 2400/2850 Hz at 2 Hz

10111

10

Int. Tone of 970 Hz at 1 Hz

10110

Back-Up Alarm(LF)

11

Alt. Tones 800/970 Hz at 7/8 Hz

10101

12

Int. Tone at 2850 Hz at 1Hz

10100

Back Up Alarm(HF)

13

970Hz at 1/4 sec on 1 sec off

10011

14

Continuous at 970 Hz

10010

15

554Hz for 100ms / 440 Hz for 400ms

10001

French Fire Sound

16

Int. 660 Hz 150 ms on 150 ms off

10000

Swedish Fire Alarm

17

Int. 660 Hz 1.8 sec on 1.8 sec off

01111

Swedish Fire Alarm

18

Int. 660 Hz 6.5 sec on 13 sec off

01110

Swedish Fire Alarm

19

Continuous 660 Hz

01101

Swedish Fire Alarm

20

Alt 554/440 Hz at 1 Hz

01100

Swedish Fire Alarm

21

Int. 660 Hz at 7/8 Hz

01011

Swedish Fire Alarm

22

Int. 2850 Hz 150 ms on 100 ms off

01010

Pelican Crossing

23

Sweep 800-970 Hz at 50 Hz

01001

Low Freq. Buzz

24

Sweep 2400-2850 Hz at 50 Hz

01000

High Freq. Buzz

25

3 970Hz pulses 0.5on/0.5off, 1.5 off

00111

26

3 2850Hz pulses 0.5on/0.5off, 1.5 off

00110

27

Int. 3100 Hz 0.32s on / 0.68s off

00101

28

Spare/Customer Tone

00100

29

Spare/Customer Tone

00011

30

Spare/Customer Tone

00010

31

Spare/Customer Tone

00001

32

Spare/Customer Tone

00000