Installation instructions, Maintenance – Edwards Signaling Genesis Chime User Manual

Page 2

Advertising
background image

2 / 2

27MAY03

P/N: 3100561 REV: 1.0

Table 2: Operating current in (Amp RMS)

High

db

Low

db

16 Vdc

0.030

0.019

24 Vdc

0.043

0.026

33 Vdc

0.045

0.027

16 Vfwr

0.060

0.040

24 Vfwr

0.076

0.049

33 Vfwr

0.081

0.055

Vdc = Volts direct current, regulated and filtered
Vfwr = Volts full wave rectified.

Table 3: Sound level output (dBA)

Signal and voltage

High db

Low db

16 Vdc

56.9

52.5

24 Vdc

59.8

54.8

Temporal

33 Vdc

60.1

55.0

16 Vdc

58.2

52.8

24 Vdc

60.8

55.6

Steady

33 Vdc

61.3

56.1

dBA = Decibels, A-weighted

UL464: Sound level output at 10 ft (3.05 m) measured in a
reverberant room.

Installation instructions

Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field
wires around the terminals.

To install the chime:

1. Remove the cover by depressing both tabs on the top of

the unit with a small screwdriver and twisting slightly.

2. Set the chime signal, sound output level, and desired

operation settings. See Figure 1.

3. Connect the chime terminals to the signal circuit field

wiring. You must observe polarity for the unit to function
properly.

For constant non-coded voltage operation, see Figure 2.

For single-stroke coded voltage operation, see Figure 3.

4. Mount the unit onto a compatible electrical box, making

sure not to over tighten the mounting screws.

5. Replace the cover by aligning at the bottom, then

snapping in at the top.

6. Test the unit for proper operation.

Maintenance

This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.

Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.

J2 J3

J1

To change the chime

from steady to temporal cut

from circle J1 to edge of

circuit board

signal

To change the chime

from non-coded to coded (single-

stroke)

operation

cut from circle J2 to edge

of circuit board

To change the chime

from high dB to

low dB cut J3 trace between

holes

sound

output level

Figure 1: Chime settings

Note: Polarity shown in alarm condition

To next device or
end of line device

-

+

-

+

From compatible fire
alarm control panel

+

-

+

-

Figure 2: Constant non-coded voltage operation

Genesis device with

Genesis Signal Master

[1]

-

+

HS

-

+

To next device or

end of line device

Continuous

power source
Coded power

source

+

+

-

-

+

-

Figure 3: Single-stroke coded voltage operation

Advertising