Specifications – Edwards Signaling FSRSI Remote System Indicator User Manual

Page 2

Advertising
background image

2 / 2

P/N 3101034 • REV 02 • REB 25JAN13

Notes

1. All wiring is supervised and power-limited

[2] AUX power supplied by the control panel can’t exceed 0.5

A. If more than 0.5 A is required, you must use a power-
limited and regulated 24 VDC auxiliary/booster power
supply that is UL/ULC Listed for fire protective signaling
systems.

[3] If powered from an external supply, the supply must be

installed in the same room as the control panel and their
24 VDC commons (−) wired together

Figure 2: Installing the FSRSI in a single-gang electrical box

Specifications


Voltage

18.8 to 27.3 VDC

Current
Standby
Alarm


17 mA at 24 VDC
56 mA at 24 VDC

Circuit capacitance

0.03 µF, max.

Circuit resistance

13 ohms, max.

Ground fault impedance

0 Ω

Wire size

12 to 18 AWG (0.75 to 2.5 sq mm)

Compatible electrical box

ANSI/NEMA OS1-1996, 1- to 4-gang
electrical box

LED indicators

AC power (green), alarm (red),
supervisory (yellow), trouble (yellow),
ground fault (yellow)

Buzzer operation

Steady (trouble event), temporal (alarm
event), slow pulse (supervisory event),
intermittent (AC fail event)

Operating environment
Temperature
Relative

Humidity


32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing

Compatible 1-gang electrical box

FSRSI

FSAT1