Wiring – Edwards Signaling GCI Graphic Annunciator Interface Card User Manual

Page 2

Advertising
background image

2 / 14

P/N 3100973-ML • REV 2.0 • ISS 16MAR11

Table 2: Baud rate settings

S1-6 Description

I

All other baud rates

O 9600

baud

(default)

I = ON, O = OFF

Annunciator circuit

Use switch segment 7 to select the annunciator circuit type as
shown in Table 3.

Table 3: Annunciator bus settings

S1-7 Description

I

Circuit supports Class B and Class A wiring

O

Circuit supports Class B and Redundant Class B wiring

I = ON, O = OFF

Wiring

Figure 1: Terminals and connectors

J1

1

8

J2

1

8

J3

1

8

J7

1

12

J4

1

8

J8

1

12

J5

1

8

J6

1

8

TB1

TB2

J15

EXTSW

S1

Figure 2: Annunciator circuit wiring

1

2

CH1(+)_IN
CH1(- )_IN

CH1(+)_OUT
CH1(- )_OUT

CH2(+)_IN
CH2(- )_IN

CH2(+)_OUT
CH2(- )_OUT

1. CH1_IN+/− from the control panel or previous annunciator.

CH1_OUT+/− to the next annunciator or to the control panel if the
last annunciator on a Class A circuit.

2. CH2_IN+/− from the control panel or previous annunciator.

CH2_OUT+/− to the next annunciator. Used only on redundant
Class B circuits.

Figure 3: AUX power riser wiring

24V(+)_IN
24V(- )_IN

24V(+)_OUT
24V(- )_OUT

1

1.

Use the control panel power supply or a 24 VDC, continuous,
regulated, power supply that is UL/ULC Listed for fire protective
signaling systems.