Edwards Signaling 116EXMLED Series User Manual

Installation, Warning

Advertising
background image

Installation Instructions for 116EXMLED Series

AdaptaBeacon

®

LED Lights for Use in Hazardous

Locations

Description

The 116EXMLED Series AdaptaBeacon LED signaling appliances

are intended for general utility signaling use. When assembled

with an available mounting subassembly (116EX-P, 116EX-C,

116EX-S, or 116EX-C with 116EX-B) and in accordance with

these instructions, the 116EXM LED visual signal is UL Listed as

a Visual Signal Appliance. The 116EXMLED is

UL and cUL listed

for use in Class I, Division 1, Groups C and D, Class I, Division 2,

Groups A, B, C and D, Class II, Division 1, Groups E, F and G,

Class II, Division 2, Groups F and G, and Class III Division 1 and

2 hazardous locations with operating temperature codes per

Table 2.

The beacons are UL and cUL Listed for outdoor use with

Type 3R, 4X, and Marine rated enclosures.

The LED beacon flashes a 360-degree beam of light with 14 user

selectable flash patterns.

The LED beacons are available in pendant, bracket, ceiling, or

stanchion mount models (Figure 1).

Installation

5 full threads and then tighten the set-screw to secure

the pendant mount module to the conduit. Make

electrical connections in accordance with Figure XX.

Refer to Table 2 for required supply wire temperature

ratings.

b. Ceiling Mount Models (Figure 3): Install the catalog

number 116EX-C, ceiling/wall mounting module, using

appropriate hardware (not supplied) suitable for the

mounting surface. Make electrical connections in

accordance with Figure 6. Refer to Table 2 for required

supply wire temperature ratings. Install main housing

to ceiling mount module. Tighten the set-screw to

secure the 116EXMLED main housing to the ceiling

mount module.

c. Bracket Mount Models (Figure 4): Install the catalog

number 116EX-C ceiling/wall mounting module using

appropriate hardware (not supplied) for the mounting

surface. Connect field earth ground wire to ground

screw or earth ground via conduit system. Install

the catalog number 116EX-B wall mounting elbow to

the 116EXMLED main housing (feed the units wiring

through the 116EX-B elbow). Tighten the set-screw to

secure the 116EX-B elbow to the main housing. Make

electrical connections in accordance with Figure 6.

Refer to Table 2 for required supply wire temperature

ratings. Install main housing and 116EX-B elbow

subassembly to ceiling mount module. Tighten the

set-screw to secure the 116EX-B elbow to the ceiling

mount module.

d. Stanchion Mount Models (Figure 5): Install the catalog

number 116EX-S, stanchion mount module to the main

housing and tighten set-screw. Mount the 116EX-S to

the 1-1/4" conduit, tighten set-screw. Ensure conduit

is connected to the appropriate junction box. Install

the unit on the conduit. Make electrical connections in

accordance with Figure 6. Refer to Table 2 for required

supply wire temperature ratings.

WARNING

To reduce the risks of ignition of hazardous

atmospheres and shock, do not apply power to

the unit until installation has been completed

and unit is tightly assembled and secured.

Install this unit in accordance with the applicable requirements

in the latest edition of the National Electrical Code and Canadian

Electrical Code.

1. Mount using the following applicable method.

a. Pendant Mount Models (Figure 2): Install the catalog

number 116EX-P, pendant mounting module, to the

main housing, tighten set-screw. Install explosion-proof

hanger box (not supplied). Secure 3/4" (19 mm) NPT

threaded conduit (not supplied) to the box. Install the

unit on the conduit. Ensure conduit engages at least

P/N 3101456 ISSUE 1 © 2008

CEILING 116EX-C

3/4" CONDUIT

ENTRIES

PENDANT 116EX-P

3/4" CONDUIT

ENTRY

116EX-C

(WALL MOUNTED)

3/4" CONDUIT

ENTRIES

116 SERIES HOUSING AND GLOBE

ASSEMBLY WITH GUARD

WALL 116EX-B

3" HUB

1 1/4"CONDUIT

ENTRY

STANCHION 116EX-S

Figure 1. Mounting Options

PLAINVILLE, CT 800-336-4206 FAX 800-454-2363