Installation guidelines, Verify the duct air velocity, Select the appropriate sampling tube – Edwards Signaling E-PDD User Manual

Page 2

Advertising
background image

2 / 6

P/N 3101210 • REV 02 • ISS 28JAN13

Installation guidelines

To ensure correct operation, install the duct detector using the
following guidelines:

Install the duct smoke detector on a flat section of HVAC
duct between six and ten duct widths from any bends or
obstructions.

Install supply-side detectors at a point downstream from
the supply fan and after the air filter.

Install return-side detectors at a point before the return air
stream is diluted by outside air.

Verify the duct air velocity

In order to verify airflow direction and velocity, air must be
moving through the HVAC system.

To verify the duct air velocity:

1. Drill a small hole at the point where the duct smoke

detector is being installed.

2. Using the SD-VTK Air Velocity Test Kit and a suitable air

velocity meter, verify that the air velocity in the HVAC duct
falls within the specified operating range of the detector
and note which direction the air flows.

3. If the air velocity does not fall within the specified range,

relocate the detector and seal the hole in the HVAC duct.
Refer to Technical Bulletin P/N 3101212 for additional
information pertaining to installation locations.

Select the appropriate sampling tube:

Select a sampling tube that extends at least two-thirds
across the width of the duct.

For duct widths greater than 36 inches, use a sampling
tube that is longer than the width of the duct.

Sampling tubes are available in the following lengths:

Model

Description

SD-T8

8-inch sampling tube

SD-T18

18-inch sampling tube

SD-T24

24-inch sampling tube

SD-T36

36-inch sampling tube

SD-T42

48-inch sampling tube

SD-T60

60-inch sampling tube

SD-T78

78-inch sampling tube

SD-T120

120-inch sampling tube

To assemble the detector:

1. Assemble the duct smoke detector as shown in Figure 2.

2. Rotate the air sampling tube so the inlet holes face the

direction of airflow.

3. The sampling tube is normally installed from the rear, but it

can also be installed from the front of the detector as
shown in Figure 3. This method requires that you remove
the detector cover.

Figure 2: Duct detector assembly

Detector

Sampling tube

socket

Exhaust tube

Thick

gasket

Thin

gasket

Exhaust tube

socket

Coupling

Sampling tube
(ordered separately)

Plug

Figure 3: Sampling tube installation

Sampling tube

connector

Sampling tube

(fully assembled)

Detector

To install the detector:

1. Attach the drill template to the HVAC duct at desired

mounting location.

2. Drill (or punch) the mounting holes where indicated.

Note:

Sampling tubes longer than 36 inches must be

supported at both ends of the duct.

3. If using an air sampling tube that is longer than the width

of the duct, drill a 3/4-inch hole on the opposite side of the
duct for tube to pass through.

4. Remove any rough edges from the holes.