Specifications – Edwards Signaling E-PDD User Manual

Page 6

Advertising
background image

6 / 6

P/N 3101210 • REV 02 • ISS 28JAN13

Specifications

Communication line voltage

Maximum 20 V peak-to-peak

Operating current

Normal
Alarm
Inrush


45 µA
45 µA
1 mA

Common alarm
relay/auxiliary equipment

Unsupervised and power-limited
Quantity: 1
Type: Form C
Ratings: 2.0 A at 30 VDC (resistive)

Air velocity

100 to 4,000 ft./min

Air pressure differential

0.005 to 1.00 inches of water

Smoke sensitivity range

0.79 to 2.46%/ft. obscuration

Smoke detection method

Photoelectric (light scattering
principle)

Alarm test response time

5 seconds

Dimensions

8.70 x 5.45 x 1.90 inches

Operating environment

Temperature
Humidity


32 to 122°F (0 to 50°C)
0 to 93% RH, noncondensing

Wire size

14 to 22 AWG wire

Detector address

01 to 64 (64 point control panel)

01 to 127 (127 point control panel)

Accessories

SD-TRM
SD-TRK
SD-MAG
SD-VTK
R-LED


Remote test-reset station, magnetic
Remote test-reset station, keyed
Test magnet kit
Air velocity test kit
Remote LED alarm indicator