Maintenance, Specifications – Edwards Signaling Integrity Synchronized Temporal Horn-Strobe User Manual

Page 3

Advertising
background image

P/N 3100376 • REV 6.0 • ISS 06MAY11

3 / 6

Figure 2: Typical one-circuit wiring diagram

(1)

(2)

NAC +

NAC +

NAC –

NAC –

Polarity is shown in the active state.

(1) From UL/ULC Listed fire alarm control panel signal circuit.
(2) To next device or end of line resistor for Class B. Return to control

panel for Class A connection.

Figure 3: Typical two-circuit wiring diagram

(1)

(2)

NAC1 +

NAC1 +

NAC2 +

NAC2 +

NAC1 –

NAC1 –

NAC2 –

NAC2 –

Polarity is shown in the active state.

(1) From UL/ULC Listed fire alarm control panel signal circuit.
(2) To next device or end of line resistor for Class B. Return to control

panel for Class A connection.

Mounting the electrical box

Figure 1 shows mounting details for:

Standard box. When using a 4 in. square box, use an
extension ring for additional wiring space, if needed. If
using a double-gang electrical box that is 2-1/2 in.
(64 mm) deep, locate the conduit only at the rear of the
box.

Weatherproof box. Peel off the adhesive backing from the
gasket and adhere to the box.

Surface mount box.

Selecting the volume and tone

The horn has a jumper for selecting a high or low volume
output level. The default is high volume. To set the output to
low volume, remove the output jumper from the circuit board
on the rear of the unit. See Figure 4 below.

The horn has a jumper for selecting either a temporal or steady
tone. The default is temporal tone. To set the output to steady
tone, remove the tone jumper from the circuit board on the rear
of the unit.

Tip:

Save the jumper by sliding it onto a single pin.

Figure 4: Jumper setup and terminal block

REMOVE FOR

LOW OUTPUT

REMOVE FOR

CONT. TONE

HORN

+

HORN

STROBE +

STROBE –

1

2

3

4

(1)

(2)

Item In

Out

(1)

High output

Low output

(2) Temporal

tone

Steady

(continuous)

tone

Maintenance

Note:

Do not change the factory-applied finishes.

This unit is shipped from the factory as an assembled unit; it
contains no user-serviceable parts and should not be
disassembled.

Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.

Specifications


Operating voltage

16 to 33 VDC, 16 to 33 VFWR

Strobe operating current See Table 4

Horn operating current

See Table 5

Sound output

See Table 6 and Table 7

Light output

See Table 10

Horn temporal pattern

0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s
on, 1.5 s off, repeat cycle

Wire size

12 to 18 AWG (0.75 to 2.50 mm²)

Compatible electrical
boxes

2-1/2 in. (64 mm) deep double-gang,
4 in. square box 2-1/8 in. (54 mm) deep,
Surface or bidirectional mounting box per
Table 2

Operating temperature
Indoor
UL

outdoor

ULC

outdoor


32 to 120°F (0 to 49°C)
−35 to 150°F (−37 to 66°C)
−40 to 150°F (−40 to 66°C)

Relative humidity
Indoor
Outdoor


93% noncondensing
98% noncondensing

Advertising