Specifications, Contact information – Edwards Signaling 5530MD-24AW User Manual

Page 6

Advertising
background image

6 / 24

P/N 3100007 • REV 07 • ISS 02JUL12

Tone

SW4-6 SW4-5 SW4-4 SW4-3 SW4-2 SW4-1 Description

HEX

Yellow Rose of Texas 

19.34 seconds of melody followed by 1 second
delay and repeat

3B

[1] 3 Pulse Tones are for evacuation use only. 3 Pulse Horn, 3 Pulse Air Horn, and 3 Pulse Dual Tone are used for ULC Fire installations.
Closed/On switch=
Open/Off switch=

Caution:

The use of evacuation signals on this product, that is not specifically listed for fire alarm use, is subject to the approval of

the authority having jurisdiction.

Specifications

Mechanical specifications

Weight

9 lb. (4.1 kg)

Temperature

Hazardous Locations, UL
Standard UL1604 Ambient
Temp.

Non-Hazardous Locations
Variable Ambient Temp.

-31°F to +104°F (-35°C to +40°C)

-40°F to +151°F (-40°C to +66°C)

Note: Hazardous locations and variable ambient conditions apply only
where UL Listings are accepted.

Electrical specifications

Catalog number

Voltage

Current (A) tone on

5530MD-24AW 20

VDC

0.63

24

VDC

0.74

28

VDC

1.0

31

VDC

0.85

20 VFWR 120 Hz

0.69

24 VFWR 120 Hz

0.79

Directional characteristics at power input voltage

Specification

Output sound pressure level at
3 meters

Rated on axis: 0°

85 dBA

Horizontal axis:

65 deg and 115 deg

60 deg and 125 deg

-3 dBA
-6 dBA

Vertical axis:

70 deg and 110 deg

60 deg and 125 deg

-3 dBA
-6 dBA

Wire gauge

22 to 12 AWG

Contact information

For contact information, see www.edwardssignaling.com.