Edwards Signaling 105DHIST-FJ User Manual

Warning, Warnings, Description

Advertising
background image

Installation Instructions for Cat. No. 105DHIST-FJ

Adverse Location Visual Signals

Description

The 105DHISTC-FJ (clear lens only) visual signal is a heavy duty,

reliable, 8 Joule high intensity strobe that is both UL 1971 and

CSFM listed for Special Application 20-30V DC Hearing Impaired

indoor use in compatible fire alarm systems. See Figure 6 for light

output patterns and Table 2 for operating current information.

The 105DHIST*-FJ (*with amber, blue, clear, green, magenta, and

red lenses) are Special Application 20-30V DC UL and cUL (General

Utility) and CSFM Listed (Misc. Devices/Control Unit Accesso-

ries). The units also utilize an 8 joule strobe. See Table 2 for current

information.

b. Cat. No. 105BM: Using the four supplied screws, secure

the mounting bracket to Cat. No. 105BX outlet box

attachment as shown in Figure 1. Attach the adhesive

backed gasket to the top of the 105BM mounting bracket,

being careful to line up the holes in the gasket with the

mounting holes in the outlet box.

c.

Cat. No. 105PM: Install 3/4" (19 mm) conduit. Screw the

pipe mount attachment onto the 3/4" (19 mm) conduit.

Attach the adhesive backed gasket to the top of the 105PM

pipe mount attachment (Figure 3), being careful to line up

the holes in the gasket with the mounting holes in the

outlet box.

4.

Attach the unit's wire leads to the field wiring as shown in

Figure 4.

NOTE: It is not necessary to remove the lens from the Hi-

Intensity Strobe Base to install the 105DHIST series

beacons. See Figures 1, 3 or 4.

5.

Secure the high intensity strobe base to the appropriate

mounting attachment using four screws (supplied) as shown

in Figure 3.

6.

Apply power and verify operability.

WARNING

To prevent electrical shock, do not connect power
until instructed to do so.

Installation must be in accordance with local codes. The lens should

be positioned up for outdoor applications.

1.

Select a mounting configuration (Figure 5).

NOTE: When mounting using the Cat. No. 105BM mounting

bracket, the Cat. No. 105BX outlet box attachment

must also be used as shown in Figure 1.

2.

Pull field wiring into the mounting attachment.

3.

Install the mounting attachment as follows:

Table 1. Hazardous Location Ratings

Cat. No.

Class

Division

Group

Operating Temperature

105DHIST*-FJ

I

2

A, B, C, D

T2A (280

o

C, 536

o

F)

I I

2

F, G

T3B (165

o

C, 329

o

F)

I I I

T3B (165

o

C, 329

o

F)

Installation

These strobes, when assembled in accordance with installation

instructions, constitute a UL listed Type 4X enclosure. They are

designed for use in industrial applications or in applications where

a Type 4X enclosure is required. For General Utility (non-fire alarm)

use, all units are UL and cUL Listed for Marine and outdoor visual

signaling applications. When assembled in accordance with these

instructions, 105 Series visual signals are UL listed for use in Haz-

ardous Locations with Operating Temperatures listed in Table 1.

For specification details, see Tables 2 - 3.

P/N 3100394 ISSUE 3 © 2003

CHESHIRE, CT 203-699-3300 FAX 203-699-3365 (CUST. SERV.) 203-699-3078 (TECH SERV.)

WARNINGS

The 105BX junction box, 105BM mounting bracket
and 105PM pipe mount attachments are non-conduc-
tive plastic fixtures and do not provide earth-ground
continuity when attached to metallic wiring systems.
Therefore, they are intended for use with the
105DHIST series visual signals

only when earth-

grounding is not required.

The 105BX junction box, 105BM mounting bracket
and 105PM pipe mount attachments

can be used with

metallic wiring systems

only when installed at the

end of a run.

a.

Cat. No. 105BX: Screw the outlet box attachment to the

mounting surface (Figure 1) using two screws (not

supplied) suitable for the surface. Attach the adhesive

backed gasket to the top of the 105BX mounting box,

being careful to line up the holes in the gasket with the

mounting holes in the outlet box.

*Insert lens color: A - Amber, B - Blue, C - Clear, G - Green, M - Magenta, R - Red.

Advertising