GW Instek GPS-x303 Series User Manual

Page 9

Advertising
background image

MULTI-OUTPUT POWER SUPPLY

USER MANUAL

12

5. OPERATION INSTRUCTION

5-1. Precaution

(1)

AC input

AC input should be within the range of line voltage ± 10% (230V

+10%~-6%) 50/60Hz.

WARNING. To avoid electrical shock, the power cord

protective grounding conductor must be connected to ground.

AVERTISS: Pour éviter les chocs électriques, le fil de terre du
cordon secteur doit impérativement être relié à la terre
.

(2) Installation

Avoid using the supply in a place where ambient temperature exceeds 40℃.

The heat sink located at the rear of the supply must have sufficient air space
for radiation.

CAUTION. To avoid damaging the power supply, don’t use
it in a place where ambient temperature exceeds 40
℃.


(3) Output voltage overshoot

Voltage between output terminals never exceeds the preset value when the
power is turned on or off.


5-2. Setting Current Limit

(1) Determine the maximum safe current for the device to be powered.
(2) Temporarily short the (+) and (-) terminals of the power supply together with a test

lead.

(3) Rotate the VOLTAGE control away from zero sufficiently for the CC indicator to

light.

(4) Set the meter selection switch to “A” position to select the current metering mode.
(5) Adjust the CURRENT control for the desired current limit. Read the current value

on the Ammeter.

(6) The current limit (overload protection) has now been preset. Do not change the

CURRENT control setting after this step.

(7) Remove the short between the (+) and (-) terminals and hook up for constant voltage

operation.

MULTI-OUTPUT POWER SUPPLY

USER MANUAL

13

5-3. Constant Voltage/Constant Current Characteristics

The working characteristic of these series Power Supplies is called a constant

voltage/constant current automatic crossover type. This permits continuous

transition from constant current to constant voltage modes in response to the

load change. The intersection of constant voltage and constant current modes

is called the crossover point. Fig. 5-1 shows the relationship between this

crossover point and the load.

For example, if the load is such that the power supply is operating in the

constant voltage mode, a regulated output voltage is provided. The output

voltage remains constant as the load increases, up until the point where the

present current limit is reached. At that point, the output current becomes

constant and the output voltage drops in proportion to further increases in

load. The point is indicated by the front panel LED indicators. The crossover

point is reached when the CV indicator goes off and the CC indicator comes

on.

Fig. 5-1 Constant Voltage/Constant Current Characteristic

Similarly, crossover from the constant current to the constant voltage mode
automatically occurs from a decrease in load. A good example of this would
be seen when charging a 12 volt battery. Initially, the open circuit voltage
of the power supply may be preset for 13.8 volts. A low battery will place a
heavy load on the supply and it will operate in the constant current mode,
which may be adjusted for a 1 amp charging rate. As the battery becomes
charged, and its voltage approaches 13.8 volts, its load decreases to the
point where it no longer demands the full 1 amp charging rate. This is the
crossover point where the power supply goes into the constant voltage
mode.

Advertising