6.4.1. High-resolution impedance measurement (0.1 m

)

The instrument allows measuring impedance with a high resolution next to a MT/BT
transformer by using the optional accessory IMP57. Measurement is selectable in modes
LOOP P-P, P-N, P-PE by means of the F2 key (Z2

). In case high-resolution impedance

measurement is selected with no connection of the accessory IMP57, the instrument shows a
screen similar to the following one (e.g.: Loop P-N):

LOOP

30.11.12

Z=-----

R=-----

 X=-----

IkSTD=----A

V1-2= 0V FRQ= 0.0Hz

NO IMP57

P-N Z2

FUNC

ZSTD

ICAL

RMT

For any detail regarding the use and the technical specifications of accessory IMP57,
please refer to the relevant user manual or visit the website www.ht-instruments.com.

6.4.2. "P-N" mode: measurement procedure and results

1. Select the P-N mode using the F1 key.
2. Insert the 3 Black, Green, Blue connectors of the three-pin shuko cable or of the separate

cables into the relevant instrument input terminals B1, B3, B4 (see Fig. 7, Fig. 8). In case
separate cables are used, insert alligator clips on the free cable ends.

Fig. 7: Connection for measuring Loop

impedance of single-phase/two-phase

230V system

Fig. 8: Connection for measuring Loop

impedance of three-phase 400V system


3. Insert the Shuko plug into a 230V 50Hz socket or the alligator clips onto the conductors

of the three-phase system (see Fig. 7, Fig. 8)

4. When possible, disconnect all loads connected downstreams of the measuring point since

the impedance of these users may alter test results.

5. Press the START key. The instrument carries out the test.


Advertising