6. TECHNICAL SPECIFICATIONS

6.1. TECHNICAL CHARACTERISTICS
Accuracy is calculated as ± [% reading + (number of digits) x resolution]. It is referred to a
temperature 18°C

 28°C with relative humidity <75% RH.

AC Voltage (Autorange)

Range Resolution Accuracy

Input

impedance

Bandwidth

Overvoltage

protection

4,000V 0,001V

(1.8%rdg + 8digits)

10M

50-400Hz

600V

DC/ACrms

40.00V 0.01V
400.0V 0.1V

600V 1V

(2.5%rdg + 8digits)

Integrated sensor for AC voltage detection: LED on for phase-earth voltage > 100V, 50/60Hz.

DC Voltage (Autorange)

Range Resolution Accuracy

Input

impedance

Overvoltage protection

400.0mVDC 0.1mV

(0.8%rdg+2digits)

10M

600AACrms

4.000VDC

0,001V

(1.5%rdg + 2digits)

40.00VDC 0.01V
400.0VDC

0.1V

600.0VDC

(2%rdg + 2digits)

AC Current

Range Resolution Accuracy

Overvoltage

protection

40.00A 0.01A

(2.5%rdg + 8digits)

400AACrms

400.0A 0.1A

(2.8%rdg + 8digits)

Bandwidth:

50Hz

 60Hz

Resistance and continuity test (Autorange)

Range Resolution Accuracy

Buzzer Overvoltage

protection

400.0

0.1

(1.0%rdg + 4digits)

<30

600VDC/ACrms

4.000k

0.001k

(1.5%rdg+2digits)

40.00k

0.01k

400.0k

0.1k

4.000M

0.001M

(2.5%rdg+3digits)

40.00M

0.01M

(3.5%rdg+5digits)

Continuity test current: < 0.5mA


Capacitance (Autorange)

Range Resolution Accuracy

Overvoltage

protection

40.00nF 0.01nF

(4.0%rdg+20digits)

600VDC/ACrms

400.0nF 0.1nF

(3%rdg+5digits)

4.000

F 0.001

F

4000

F 0.01

F

(4.0%rdg+10digits)

100.0

F 01

F

Diode test

Range

Test current

Open-circuit voltage

0.3mA typical

1.5VDC





Advertising