DEFINITION OF MEASUREMENT (OVERVOLTAGE) CATEGORY

Standard CEI 61010: Safety requirements for electrical equipment for measurement,
control and laboratory use, Part 1: General requirements” defines what measurement
category, commonly called overvoltage category, is. In § 6.7.4: Measured circuits, circuits
are divided into the following measurement categories:

(OMISSIS)

Measurement category IV is for measurements performed at the source of the

low-voltage installation.

Examples are electricity meters and measurements on primary overcurrent
protection devices and ripple control units.

Measurement category III is for measurements performed on installations inside

buildings.

Examples are measurements on distribution boards, circuit breakers, wiring,
including cables, bus-bars, junction boxes, switches, socket-outlets in the fixed
installation, and equipment for industrial use and some other equipment, for
example, stationary motors with permanent connection to fixed installation.

Measurement category II is for measurements performed on circuits directly

connected to the low-voltage installation.

Examples are measurements on household appliances, portable tools and similar
equipment.

Measurement category I is for measurements performed on circuits not directly

connected to MAINS.

Examples are measurements on circuits not derived from MAINS, and specially
protected (internal) MAINS-derived circuits. In the latter case, transient stresses are
variable; for that reason, the standard requires that the transient withstand
capability of the equipment is made known to the user.